340
JOHNSON CONTROLS
FORM 201.21-NM3 (616)
COMPRESSOR MOTOR OVERLOAD & MAX. VSD FREQUENCY
TABLE 34 - COMPRESSOR MOTOR OVERLOAD SETTINGS & MAX. VSD FREQUENCY
MAINTENANCE
3 COMP CHILLER MODELS WITH STANDARD (PIN 52 = X) AND ULTRA QUIET (PIN 52 = L) FANS
CHILLER MODEL
(3 COMP)
W/ STD &
UQ FANS
CHILLER NAME-
PLATE VOLTAGE
(VAC)
COMPRESSOR
1 OVERLOAD
SETTING
(AMPS)
COMPRESSOR
2 OVERLOAD
SETTING
(AMPS)
COMPRESSOR
3 OVERLOAD
SETTING
(AMPS)
MAXIMUM VSD
FREQUENCY
(HZ)
YCAV0267EA/VA
380,460,575
244
244
191
182
YCAV0287EA/VA
380,460,575
242
242
242
178
YCAV0287SA/PA
380,460,575
246
273
192
186
YCAV0307SA/PA
380,460,575
248
248
274
188
YCAV0327EA/VA
380,460,575
250
250
234
192
YCAV0357EA/VA
380,460,575
289
289
232
192
YCAV0357SA/PA
380,460,575
254
254
289
200
YCAV0397SA/PA
380,460,575
289
289
289
200
4 COMP CHILLER MODELS WITH STANDARD (PIN 52 = X) FANS
CHILLER
MODEL
(4 COMP)
W/ STD FANS
CHILLER
NAMEPLATE
VOLTAGE
(VAC)
COMPRESSOR
1 OVERLOAD
SETTING
(AMPS)
COMPRESSOR
2 OVERLOAD
SETTING
(AMPS)
COMPRESSOR
3 OVERLOAD
SETTING
(AMPS)
COMPRESSOR
4 OVERLOAD
SETTING
(AMPS)
MAXIMUM
VSD
FREQUENCY
(HZ)
YCAV0397EA/VA
380,460,575
241
241
241
241
178
YCAV0417EA/VA
380,460,575
234
234
250
250
192
YCAV0417SA/PA
380,460,575
251
251
251
251
196
YCAV0457SA/PA
380,460,575
289
289
248
248
192
YCAV0477EA/VA
380,460,575
289
289
232
232
192
YCAV0477SA/PA
380,460,575
289
289
254
254
200
YCAV0507SA/PA
380,460,575
289
289
253
289
200
YCAV0527SA/PA
380,460,575
289
289
289
289
200
Summary of Contents for YCAV0267E
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Page 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Page 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Page 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Page 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Page 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Page 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Page 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Page 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...