42
JOHNSON CONTROLS
FORM 201.21-NM3 (616)
TECHNICAL DATA
6
GLYCOL CORRECTION FACTORS
The cooler is designed in accordance with ARI-
590-92 which allows for an increase in pressure
drop of up to 15% above the design value shown
on page 40. Debris in the water may also cause
additional pressure drop.
When using glycol solutions, pressure drops are
higher than with water (see correction factors to be
applied when using glycol solutions). Special care
must be taken not to exceed the maximum flow
rate allowed.
A= Correction Factor
B= Mean Temperature through Cooler
C= Concentration W/W
Excessive flow, above the max. GPM,
will damage the evaporator.
PROPYLENE GLYCOL
ETHYLENE GLYCOL
GLYCOL CORRECTION FACTORS
A
A
B
B
18
17
16
15
14
13
12
11
10
1.45
1.40
1.35
1.30
1.25
1.20
1.15
1.10
1.05
50%
40%
30%
20%
10%
50%
40%
30%
20%
10%
C
C
-10 -8 -6 -4 -2 0 2 4 6 8 C
-10 -8 -6 -4 -2 0 2 4 6 8 C
LD10500
Summary of Contents for YCAV0267E
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Page 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Page 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Page 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Page 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Page 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Page 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Page 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Page 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...