TABLE 36 -
OUTSIDE AIR TEMPERATURE SENSOR INPUT VOLTAGE (MEASURED SIGNAL TO SHIELD AT
THE SENSOR)
TEMP. (ºF)
VOLTAGE
TEMP. (ºF)
VOLTAGE
TEMP. (ºF)
VOLTAGE
0.24
0.68
49.8
2.00
93.3
3.31
1.79
0.71
50.7
2.03
94.4
3.34
3.30
0.74
51.6
2.06
65.6
3.37
4.76
0.77
52.5
2.09
96.8
3.40
6.19
0.80
53.4
2.11
98.0
3.43
7.58
0.83
54.3
2.14
99.2
3.46
8.94
0.85
55.3
2.17
100.4
3.49
10.3
0.88
56.2
2.20
101.6
3.52
11.6
0.91
57.1
2.23
102.9
3.55
12.8
0.94
58.0
2.26
104.2
3.57
14.1
0.97
58.9
2.29
105.5
3.60
15.3
1.00
59.8
2.32
106.8
3.63
16.5
1.03
60.7
2.35
108.1
3.66
17.7
1.06
61.6
2.38
109.5
3.69
18.9
1.09
62.6
2.41
110.9
3.72
20.0
1.12
63.5
2.44
112.3
3.75
21.2
1.15
64.4
2.47
113.8
3.78
22.3
1.18
65.3
2.50
115.2
3.81
23.4
1.21
66.3
2.52
116.7
3.84
24.4
1.24
67.2
2.55
118.3
3.87
25.5
1.26
68.1
2.58
119.9
3.90
26.6
1.26
69.1
2.61
121.5
3.93
27.6
1.32
70.0
2.64
123.2
3.96
28.7
1.35
70.9
2.67
124.9
3.98
29.7
1.38
71.9
2.70
126.6
4.01
30.7
1.41
72.8
2.73
128.4
4.04
31.7
1.44
73.8
2.76
130.3
4.07
32.7
1.47
74.8
2.76
33.7
1.50
75.8
2.82
34.7
1.53
76.7
2.85
35.7
1.56
77.7
2.88
36.7
1.59
78.7
2.91
37.6
1.62
79.7
2.93
38.6
1.65
80.7
2.96
39.6
1.67
81.7
2.99
40.5
1.70
82.7
3.02
41.4
1.73
83.6
3.05
42.4
1.76
84.6
3.08
43.3
1.79
85.7
3.11
44.3
1.82
86.7
3.13
45.2
1.85
87.8
3.16
46.1
1.88
88.9
3.19
47.0
1.91
90.1
3.22
48.0
1.94
91.1
3.25
48.9
1.97
92.2
3.28
Summary of Contents for YCIV Series
Page 14: ...JOHNSON CONTROLS 14 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 32: ...JOHNSON CONTROLS 32 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 40: ...JOHNSON CONTROLS 40 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 325: ...JOHNSON CONTROLS 325 FORM 201 23 NM2 ISSUE DATE 09 25 2020 NOTES...