MODEL: YCIV1220E/V
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25.0
30.0
35.0
40.0
45.0
46.0
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
5.0
1082.7 247.9
3.9
1064.7 284.7
3.4
1044.3 326.4
3.0
1013.0 371.0
2.6
945.2
394.1
2.3
930.6
397.6
2.2
6.0
1113.5 249.6
4.0
1094.7 285.8
3.5
1073.2 327.3
3.0
1038.5 371.1
2.6
967.8
394.2
2.3
953.0
397.8
2.2
7.0
1145.0 251.6
4.1
1125.3 287.1
3.6
1102.8 328.3
3.1
1064.7 371.1
2.7
991.1
394.1
2.4
975.8
397.9
2.3
8.0
1177.1 253.9
4.2
1156.5 288.5
3.7
1133.0 329.5
3.2
1091.4 371.0
2.7
1014.9 393.9
2.4
999.0
397.7
2.4
9.0
1209.8 256.5
4.3
1188.4 290.3
3.8
1164.0 330.7
3.3
1118.6 370.9
2.8
1039.0 393.5
2.5
1022.8 397.4
2.4
10.0
1243.2 259.3
4.3
1221.0 292.3
3.8
1195.5 332.2
3.3
1146.4 370.9
2.9
1063.6 393.0
2.5
1047.0 397.0
2.5
11.0
1277.2 262.6
4.4
1254.2 294.7
3.9
1227.8 333.8
3.4
1174.3 370.9
3.0
1088.5 392.5
2.6
1071.6 396.5
2.5
12.0
1311.9 266.1
4.5
1288.1 297.2
4.0
1260.7 335.7
3.5
1201.8 370.4
3.0
1114.1 391.9
2.7
1085.7 389.4
2.6
13.0
1347.3 270.1
4.5
1322.6 300.0
4.1
1294.1 337.9
3.6
1229.8 370.1
3.1
1139.9 391.3
2.7
1095.0 379.4
2.7
MODEL: YCIV1380E/V
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25.0
30.0
35.0
40.0
45.0
46.0
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
5.0
1228.4 287.0
3.9
1206.7 325.4
3.4
1181.0 367.8
3.0
1146.5 415.9
2.6
1083.9 450.5
2.3
1070.4 456.8
2.2
6.0
1263.2 289.6
4.0
1241.1 327.6
3.5
1214.5 370.0
3.0
1177.1 417.5
2.6
1111.7 451.6
2.3
1097.6 457.9
2.3
7.0
1298.8 292.2
4.0
1276.1 330.0
3.5
1248.7 372.3
3.1
1208.5 419.0
2.7
1139.9 452.8
2.4
1125.5 459.0
2.3
8.0
1334.9 295.0
4.1
1311.8 332.6
3.6
1283.4 374.9
3.2
1240.5 420.6
2.8
1168.8 453.8
2.4
1153.8 460.1
2.4
9.0
1371.6 298.1
4.2
1348.0 335.4
3.7
1318.9 377.4
3.2
1273.1 422.2
2.8
1198.3 454.9
2.5
1183.0 461.2
2.4
10.0
1409.1 301.3
4.3
1384.9 338.3
3.8
1355.0 380.2
3.3
1306.1 424.0
2.9
1228.4 456.0
2.5
1205.0 457.4
2.5
11.0
1447.1 304.6
4.3
1422.5 341.3
3.8
1391.8 383.1
3.4
1339.8 425.7
2.9
1258.9 457.1
2.6
1215.9 446.2
2.6
12.0
1485.7 308.3
4.4
1460.6 344.7
3.9
1429.2 386.1
3.4
1372.9 427.0
3.0
1290.1 458.2
2.6
1226.3 435.1
2.6
13.0
1525.2 311.0
4.5
1499.4 348.1
4.0
1467.3 389.3
3.5
1406.5 428.4
3.1
1308.1 450.8
2.7
1236.0 424.3
2.7
NOTES:
1. kWo
= Unit kW Cooling Capacity Output
2. kWi
= Compressor kW Input
3. COP
= Coefficient of Performance (includes condenser fan power)
4. LCWT = Leaving Chilled Water Temperature
5. Ratings based on 0.168 l/s cooler water per ton, and 0.018 (m
2
– °C)/kW
6. AHRI 550/590 does not provide certification for 50Hz ratings. The unique use of the YCIV variable speed drive allows compressor operation at the output speed regardless of the input
power frequency. This allows for common unit/heat exchanger configurations between 60Hz and 50Hz with closely matching capacity.
Summary of Contents for YCIV
Page 27: ...JOHNSON CONTROLS FORM 201 23 EG2 713 27...
Page 29: ...JOHNSON CONTROLS FORM 201 23 EG2 713 29...
Page 31: ...JOHNSON CONTROLS FORM 201 23 EG2 713 31...
Page 33: ...JOHNSON CONTROLS FORM 201 23 EG2 713 33...
Page 35: ...JOHNSON CONTROLS FORM 201 23 EG2 713 35...
Page 37: ...JOHNSON CONTROLS FORM 201 23 EG2 713 37...
Page 39: ...JOHNSON CONTROLS FORM 201 23 EG2 713 39...
Page 41: ...JOHNSON CONTROLS FORM 201 23 EG2 713 41...
Page 43: ...JOHNSON CONTROLS FORM 201 23 EG2 713 43...
Page 45: ...JOHNSON CONTROLS FORM 201 23 EG2 713 45...
Page 47: ...JOHNSON CONTROLS FORM 201 23 EG2 713 47...
Page 55: ...JOHNSON CONTROLS FORM 201 23 EG2 713 55 INTENTIONALLY LEFT BLANK...
Page 68: ...JOHNSON CONTROLS 68 FORM 201 23 EG2 713 Typical Control Wiring Two Compressor...
Page 70: ...JOHNSON CONTROLS 70 FORM 201 23 EG2 713 Typical Control Wiring Three Compressor...
Page 72: ...JOHNSON CONTROLS 72 FORM 201 23 EG2 713 Typical Control Wiring Four Compressor...