JOHNSON CONTROLS
24
FORM 201.23-EG2 (713)
Physical Data (SI - High Efficiency)
REFRIGERANT R-134A
HIGH EFFICIENCY
MODEL NUMBER (YCIV____ E/V)
50HZ
0590
0630
0700
0760
0800
0830
0930
NUMBER OF INDEPENDENT REFRIGERANT CIRCUITS
2
2
2
2
2
2
2
REFRIGERANT CHARGE, R-134A, CKT.-1/CKT.-2, KG.
77/77
84/77
84/84
87/87
102/87
102/102
105/105
OIL CHARGE, CKT.-1/CKT.-2, LITERS
19/19
19/19
19/19
19/19
19/19
19/19
19/19
COMPRESSORS, SEMIHERMETIC SCREW QTY PER CHILLER
2
2
2
2
2
2
2
CONDENSERS, HIGH EFFICIENCY FIN/TUBE WITH INTEGRAL SUBCOOLER
TOTAL CHILLER COIL FACE AREA, M
2
21.8
24.5
27.2
27.2
30.0
32.7
32.7
NUMBER OF ROWS
3
3
3
3
3
3
3
FINS PER METER
669
669
669
669
669
669
669
CONDENSER FANS
NUMBER, CKT.-1/CKT.-2
4/4
5/4
5/5
5/5
6/5
6/6
6/6
LOW SOUND FANS
FAN MOTOR, HP/KWI
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
TOTAL CHILLER AIRFLOW, L/SEC.
49082
55218
61353
61353
67488
73624
73624
ULTRA QUIET FANS
FAN MOTOR, HP/KWI
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
TOTAL CHILLER AIRFLOW, L/SEC.
49082
55218
61353
61353
67488
73624
73624
DUAL SPEED FANS - NORMAL SPEED
FAN, KWI
1.5
1.5
1.5
1.5
1.5
1.5
1.5
TOTAL CHILLER, M
3
/S
42
47
52
52
57
62
62
DUAL SPEED FANS - LOWER SPEED
FAN, KWI
1.5
1.5
1.5
1.5
1.5
1.5
1.5
TOTAL CHILLER, M
3
/S
32
36
40
40
44
48
48
HIGH STATIC FANS
FAN, KWI
3.7
3.7
3.7
3.7
3.7
3.7
3.7
TOTAL CHILLER, M
3
/S
49
55
61
61
67
74
74
EVAPORATOR, DIRECT EXPANSION
WATER VOLUME, LITERS
359.6
359.6
359.6
416.4
416.4
416.4
529.9
MAXIMUM WATER SIDE PRESSURE, BAR
1
10
10
10
10
10
10
10
MAXIMUM REFRIGERANT SIDE PRESSURE, BAR
16
16
16
16
16
16
16
MINIMUM CHILLED WATER FLOW RATE, L/SEC.
10.1
10.1
10.1
11.4
11.4
11.4
11.4
MAXIMUM CHILLED WATER FLOW RATE, L/SEC.
47.3
47.3
47.3
47.3
47.3
47.3
50.5
WATER CONNECTIONS, INCHES
10
10
10
10
10
10
10
Contact your nearest Johnson Controls Sales Office for weight data.
Summary of Contents for YCIV
Page 27: ...JOHNSON CONTROLS FORM 201 23 EG2 713 27...
Page 29: ...JOHNSON CONTROLS FORM 201 23 EG2 713 29...
Page 31: ...JOHNSON CONTROLS FORM 201 23 EG2 713 31...
Page 33: ...JOHNSON CONTROLS FORM 201 23 EG2 713 33...
Page 35: ...JOHNSON CONTROLS FORM 201 23 EG2 713 35...
Page 37: ...JOHNSON CONTROLS FORM 201 23 EG2 713 37...
Page 39: ...JOHNSON CONTROLS FORM 201 23 EG2 713 39...
Page 41: ...JOHNSON CONTROLS FORM 201 23 EG2 713 41...
Page 43: ...JOHNSON CONTROLS FORM 201 23 EG2 713 43...
Page 45: ...JOHNSON CONTROLS FORM 201 23 EG2 713 45...
Page 47: ...JOHNSON CONTROLS FORM 201 23 EG2 713 47...
Page 55: ...JOHNSON CONTROLS FORM 201 23 EG2 713 55 INTENTIONALLY LEFT BLANK...
Page 68: ...JOHNSON CONTROLS 68 FORM 201 23 EG2 713 Typical Control Wiring Two Compressor...
Page 70: ...JOHNSON CONTROLS 70 FORM 201 23 EG2 713 Typical Control Wiring Three Compressor...
Page 72: ...JOHNSON CONTROLS 72 FORM 201 23 EG2 713 Typical Control Wiring Four Compressor...