background image

JOHNSON CONTROLS

108

FORM 201.23-EG1 (1013)

UNIT LOCATION

The YCIV chillers are designed for outdoor installation. 

When selecting a site for installation, be guided by the 

following requirements:

1.  Installation sites may be either on a roof or on ground 

level. (See 

FOUNDATION

2.  Select a place having an adequate supply of fresh air 

for the condensers. Recommended clearances for all 

units are shown on the 

DIMENSIONS

 pages.

3.  Avoid  locations  near  windows  or  structures  where 

normal operating sounds may be objectionable.

4.  The condenser fans are propeller-type and are not 

recommended for use with ductwork, filters or other 

impedements to airflow in the condenser air stream.

5.  When it is desirable to surround the unit(s), in addition 

to whatever optional louver package is selected, it is 

recommended that the screening be able to pass the 

required chiller CFM without exceeding 0.1" external 

static pressure. 

6.  Protection against corrosive environments is available 

by ordering the units with either copper fins or cured 

epoxy-coating on the condenser coils. Epoxy-coated 

coils should be utilized with any units being installed at 

the seashore, or where salt spray may hit the units, or 

where acid rain is prevalent (copper condenser coils 

are not recommended where they may be exposed 

to acid rain).

7.  On installations where winter operation is intended and 

snow accumulations are expected, additional elevation 

must be provided to insure normal condenser air flow.

FOUNDATION

The unit should be mounted on a flat and level founda

-

tion,  ground  or  roof,  capable  of  supporting  the  entire 

operating weight of the equipment. Please contact your 

nearest Johnson Controls Sales Office for shipping and 

operating weights.

Roof Locations – 

Adequate structural strength to safely 

support the entire weight of the unit and service person

-

nel must be provided. Care must be taken not to damage 

the roof during installation. If the roof is “bonded”, consult 

building contractor or architect for special installation re-

quirements. Roof installations should incorporate the use 

of spring-type isolators to minimize the transmission of 

vibration into building structure. Additional support should 

be provided to the roof at the spring-isolator locations.

Ground Locations

 

– 

Units must be installed on a sub-

stantial base that will not settle and cause strain on the 

refrigerant lines, resulting in possible leaks. A one-piece 

concrete slab, with footers extending below the frost line, 

is recommended. The slab should not be tied to the main 

building foundation as operational noise will telegraph.

Mounting holes (5/8") are provided in the base rails for 

bolting the unit to its foundation. See DIMENSIONS for 

location of the mounting holes.

For ground installations, precautions should be taken to 

protect the unit from tampering by, or injury to, unauthor

-

ized persons. Fasteners on access panels will prevent 

casual  tampering;  however,  further  safety  precautions, 

such as unit enclosure options, a fenced-in enclosure, or 

locking devices on the panels may be advisable. Check 

local authorities for safety regulations.

CHILLED LIQUID PIPING

The chilled liquid piping system should be laid out so that 

the circulating pump discharges into the cooler. The inlet 

and outlet cooler-liquid connections are given in DIMEN-

SIONS. Hand stop valves are recommended for use in 

all lines to facilitate servicing. Drain connections should 

be provided at all low points to permit complete drainage 

of the cooler and system piping.

The evaporator must be protected by a strainer, preferably 

of 40 mesh, fitted as close as possible to the liquid inlet 

connection, and provided with a means of local isolation.

The evaporator must not be exposed to flushing velocities 

or debris released during flushing. It is recommended that 

a suitably sized bypass and valve arrangement is installed 

to allow flushing of the piping system. The bypass can be 

used during maintenance to isolate the heat exchanger 

without disrupting flow to other units.

Pressure-gauge connections are recommended for instal-

lation in the inlet and outlet water lines. Gauges are not 

provided with the unit and are to be furnished by others.

Chilled  liquid  lines  exposed  to  the  weather  should  be 

wrapped with a supplemental heater cable and insulated, 

or glycol should be added to the chilled liquid to protect 

against freezing if low-ambient periods are expected.

A flow switch is available as an accessory on all units. A 

flow switch must be installed in the leaving water piping of 

the cooler and must not be used to start and stop the unit.

Application Data

Summary of Contents for YCIV0157E/V

Page 1: ...FORM 201 23 EG1 1013 Model YCIV Air Cooled Screw Liquid Chillers with Variable Speed Drive Style A 150 385 TONS 527 1354 kWi 2 3 and 4 Compressor 60 Hz ASHRAE 90 1 Compliant HFC 134a 140 200 Tons 60Hz...

Page 2: ...fficiency 50 Physical Data SI Standard Efficiency 52 Physical Data SI High Efficiency 54 Dimensions English 56 Isolator Locations English 78 Isolator Locations SI 82 Isolator Details 86 Electrical Dat...

Page 3: ...onditions the chiller sound output is reduced when it is the most sensitive to neighbors evenings and weekends With the introduction of the YCIV model air cooled chiller system designers have the oppo...

Page 4: ...found with conventional motor starters In addition by eliminating the heat buildup during starting the required off time between starts is reduced to a maximum of two minutes Many utility companies ch...

Page 5: ...oviding vertical air discharge from extended orifices Guards of heavy gauge PVC polyvinyl chloride coated Standard and reduced sound level models have condensers fitted with single speed fans Low soun...

Page 6: ...et shut down for the following conditions high or low ambient low leaving chilled liquid temperature under voltage and flow switch operation COMPLETE FACTORY PACKAGE These air cooled chillers are ship...

Page 7: ...regulations it may be desirable to force the chiller to a lower sound level on demand The SilentNight control option provides a control input to limit sound output of the chiller based on time of day...

Page 8: ...T SEQUENCE CONTROL Separate se quencing control center provided to permitting control of up to eight chillers in parallel based on mixed liquid temperature interconnecting wiring by others Field mount...

Page 9: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 9 NOMENCLATURE The Model Number denotes the following characteristics of the unit Nomenclature...

Page 10: ...N CONDENSER F MIN 1 MAX 2 MIN MAX MIN MAX 60 HZ 0157 S P 40 60 140 675 0 125 0157 E V 40 60 160 750 0 125 0177 S P 40 60 160 750 0 125 0177 E V 40 60 160 750 0 125 0187 S P 40 60 160 750 0 125 0187 E...

Page 11: ...247 S P 4 4 15 6 11 4 50 5 17 8 51 7 0247 E V 4 4 15 6 10 1 47 3 17 8 51 7 0267 S P 4 4 15 6 11 4 50 5 17 8 51 7 0267 E V 4 4 15 6 11 4 50 5 17 8 51 7 0287 S P 4 4 15 6 15 8 75 7 17 8 51 7 0287 E V 4...

Page 12: ...ROLS 12 FORM 201 23 EG1 1013 Water Pressure Drop ENGLISH UNITS COOLER MODEL NUMBER YCIV 60Hz A 0157 S P B 0157 E V 0177 S P E V 0187 S P E V C 0197 E V 0207 E V 0227 E V D 0207 S P 0227 S P 0247 S P E...

Page 13: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 13 SI UNITS COOLER MODEL NUMBER YCIV 60Hz A 0157 S P B 0157 E V 0177 S P E V 0187 S P E V C 0197 E V 0207 E V 0227 E V D 0207 S P 0227 S P 0247 S P E V 0267 S P...

Page 14: ...z A 0267EA VA 0287SA PA 0287EA VA B 0307SA PA 0327EA VA 0357SA PA 0357EA VA 0397SA PA C 0457PA Water Pressure Drop ENGLISH UNITS 1 10 100 100 1000 Water Flow Rate GPM Pressure Drop ft H2O 2000 A B C P...

Page 15: ...LS FORM 201 23 EG1 1013 15 SI UNITS C Pressure Drop Through Three and Four Circuit YCIV Evaporators EVAP YCIV MODELS 60Hz A 0267EA VA 0287SA PA 0287EA VA B 0307SA PA 0327EA VA 0357SA PA 0357EA VA 0397...

Page 16: ...206 2 8 7 154 0 215 3 8 1 147 5 222 8 7 5 131 8 207 2 7 2 44 0 176 1 146 8 13 2 174 6 158 3 12 2 172 8 170 6 11 3 170 7 183 5 10 4 168 4 196 8 9 6 163 8 206 8 8 9 158 3 215 8 8 3 151 5 223 4 7 7 133...

Page 17: ...213 7 11 8 224 6 229 3 11 0 221 8 245 9 10 1 217 5 262 2 9 4 208 9 270 2 8 7 200 3 277 7 8 2 191 8 284 7 7 6 48 0 238 9 187 8 14 0 236 7 201 1 13 0 234 2 215 4 12 1 231 4 231 0 11 2 228 5 247 5 10 4...

Page 18: ...1 6 13 5 282 6 249 6 12 5 279 6 269 2 11 5 276 3 290 0 10 6 272 7 311 7 9 8 266 3 330 6 9 1 257 7 346 2 8 4 246 8 357 8 7 8 214 8 318 9 7 6 45 0 289 6 232 6 13 7 286 9 250 5 12 6 283 9 270 0 11 7 280...

Page 19: ...MODEL YCIV0397S P S_IPLV 13 2 P_IPLV 15 2 AIR TEMPERATURE ON CONDENSER F LCWT F 75 80 85 90 95 100 105 110 115 TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS...

Page 20: ...1 9 3 151 2 196 5 8 6 146 1 207 9 7 9 139 9 218 6 7 2 44 0 167 6 129 9 13 9 166 3 139 3 12 9 164 8 149 5 12 0 163 2 160 4 11 2 161 5 171 9 10 4 159 4 185 0 9 6 155 6 197 2 8 8 150 1 208 5 8 1 143 6 2...

Page 21: ...4 190 8 12 5 215 1 205 4 11 5 212 8 221 1 10 7 210 0 239 2 9 8 204 8 253 1 9 1 197 1 262 0 8 4 189 0 269 7 7 9 48 0 228 1 168 1 14 7 226 1 179 3 13 7 224 0 192 2 12 8 221 7 206 5 11 8 219 2 222 0 10 9...

Page 22: ...4 1 278 8 231 4 13 1 276 0 249 2 12 1 272 9 268 5 11 2 269 5 288 9 10 4 265 6 312 2 9 5 258 9 331 4 8 8 247 9 343 6 8 1 237 1 355 1 7 5 45 0 285 5 216 3 14 3 283 1 232 3 13 3 280 3 249 9 12 3 277 2 26...

Page 23: ...MODEL YCIV0357E V E_IPLV 12 2 V_IPLV 15 3 AIR TEMPERATURE ON CONDENSER F LCWT F 75 80 85 90 95 100 105 110 115 TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS...

Page 24: ...7 592 6 172 3 3 2 579 1 195 9 2 8 550 1 213 8 2 4 496 5 219 2 2 1 467 9 207 4 2 1 7 0 620 4 151 6 3 8 609 2 173 3 3 3 595 2 197 0 2 8 563 9 214 3 2 5 502 4 215 2 2 2 474 0 203 7 2 2 8 0 637 4 152 7 3...

Page 25: ...2 3 676 0 284 4 2 2 9 0 835 5 192 8 4 0 819 9 218 4 3 5 802 0 247 4 3 0 758 8 268 7 2 7 702 9 282 0 2 4 690 9 283 9 2 3 10 0 858 4 194 8 4 1 842 2 220 1 3 6 823 6 248 9 3 1 776 3 268 8 2 7 719 2 282...

Page 26: ...2 1 2 3 770 3 313 8 2 3 9 0 1059 7 242 7 4 0 1040 1 276 6 3 5 1013 9 313 3 3 0 962 0 344 1 2 6 827 4 325 5 2 4 778 7 307 4 2 4 10 0 1088 5 244 9 4 1 1068 4 278 3 3 6 1040 2 314 2 3 1 985 0 344 1 2 7 8...

Page 27: ...6 MODEL YCIV0397S P AIR TEMPERATURE ON CONDENSER C LCWT C 25 0 30 0 35 0 40 0 45 0 46 0 KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP 5 0 1337 3 335 1 3 7 1315 3 380 8 3 2 1289 8 430 8...

Page 28: ...5 6 2 7 528 8 215 6 2 3 520 3 219 5 2 2 9 0 623 5 136 1 4 1 613 9 153 8 3 6 602 3 173 9 3 2 581 3 196 3 2 8 541 5 216 1 2 3 532 8 220 1 2 3 10 0 640 4 137 4 4 2 630 5 154 9 3 7 618 5 174 9 3 3 596 0 1...

Page 29: ...COP KW KW COP 5 0 715 1 166 5 3 9 703 9 191 2 3 4 691 1 219 2 2 9 672 4 250 0 2 5 630 3 267 0 2 2 620 8 269 4 2 2 6 0 735 3 167 7 4 0 723 6 191 9 3 4 710 2 219 8 3 0 689 7 250 2 2 6 645 5 267 0 2 3 6...

Page 30: ...858 7 355 0 2 3 9 0 1045 2 225 6 4 2 1027 4 256 0 3 7 1005 4 291 3 3 2 967 3 328 8 2 8 894 2 351 0 2 4 879 6 355 2 2 3 10 0 1073 8 227 9 4 3 1055 6 257 6 3 8 1033 0 292 7 3 3 991 0 328 8 2 8 915 8 351...

Page 31: ...EL YCIV0357E V AIR TEMPERATURE ON CONDENSER C LCWT C 25 0 30 0 35 0 40 0 45 0 46 0 KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP 5 0 1228 4 292 9 3 8 1206 7 332 0 3 3 1181 0 375 3 2 9 11...

Page 32: ...6 159 1 202 1 8 9 154 0 211 0 8 2 147 5 218 3 7 6 131 8 203 1 7 3 44 0 176 1 143 9 13 4 174 6 155 2 12 4 172 8 167 2 11 5 170 7 179 8 10 6 168 4 192 9 9 8 163 8 202 6 9 1 158 3 211 5 8 4 151 5 218 9...

Page 33: ...13 0 227 2 209 4 12 1 224 6 224 7 11 2 221 8 240 9 10 3 217 5 257 0 9 5 208 9 264 8 8 9 200 3 272 2 8 3 191 8 279 0 7 8 48 0 238 9 184 1 14 3 236 7 197 0 13 3 234 2 211 1 12 3 231 4 226 4 11 4 228 5 2...

Page 34: ...85 2 226 9 13 8 282 6 244 6 12 7 279 6 263 8 11 7 276 3 284 2 10 8 272 7 305 5 10 0 266 3 324 0 9 2 257 7 339 3 8 6 246 8 350 7 8 0 214 8 312 5 7 7 45 0 289 6 228 0 13 9 286 9 245 5 12 9 283 9 264 6 1...

Page 35: ...374 9 481 9 8 8 364 2 503 9 8 2 350 8 519 5 7 7 46 0 413 5 327 6 13 9 410 0 350 9 12 9 406 0 376 1 12 0 401 6 402 7 11 1 396 9 430 5 10 3 390 7 460 7 9 5 380 0 482 8 8 9 369 2 504 8 8 3 352 7 513 1 7...

Page 36: ...8 181 8 9 9 157 8 193 6 9 1 152 1 204 6 8 3 145 5 215 2 7 6 46 0 172 8 128 6 14 4 171 4 137 7 13 5 169 9 147 6 12 5 168 2 158 2 11 7 166 4 169 4 10 8 164 3 182 2 10 0 160 0 194 0 9 2 154 1 204 9 8 4...

Page 37: ...9 1 194 5 256 9 8 5 186 6 264 4 7 9 46 0 221 3 162 6 14 7 219 4 174 1 13 7 217 4 187 0 12 7 215 1 201 3 11 7 212 8 216 6 10 9 210 0 234 4 10 0 204 8 248 1 9 2 197 1 256 7 8 6 189 0 264 3 8 0 48 0 228...

Page 38: ...7 306 5 9 8 262 4 324 8 9 0 251 3 336 8 8 4 240 3 348 2 7 8 46 0 289 9 213 1 14 7 287 4 228 5 13 7 284 6 245 7 12 7 281 4 264 4 11 7 277 9 284 3 10 8 273 8 307 1 9 9 266 0 324 8 9 2 254 7 336 9 8 5 24...

Page 39: ...MODEL YCIV0357E V E_IPLV 12 4 V_IPLV 15 6 AIR TEMPERATURE ON CONDENSER F LCWT F 75 0 80 0 85 0 90 0 95 0 100 0 105 0 110 0 115 0 TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EE...

Page 40: ...8 592 6 168 9 3 3 579 1 192 0 2 8 550 1 209 5 2 5 496 5 214 8 2 2 467 9 203 3 2 2 7 0 620 4 148 6 3 8 609 2 169 9 3 3 595 2 193 1 2 9 563 9 210 0 2 5 502 4 210 9 2 2 474 0 199 7 2 2 8 0 637 4 149 7 3...

Page 41: ...2 3 676 0 278 7 2 3 9 0 835 5 189 0 4 1 819 9 214 1 3 6 802 0 242 4 3 1 758 8 263 3 2 7 702 9 276 4 2 4 690 9 278 2 2 3 10 0 858 4 190 9 4 1 842 2 215 7 3 6 823 6 244 0 3 2 776 3 263 4 2 8 719 2 276...

Page 42: ...4 2 4 770 3 307 5 2 3 9 0 1059 7 237 8 4 1 1040 1 271 0 3 6 1013 9 307 0 3 1 962 0 337 2 2 7 827 4 319 0 2 4 778 7 301 3 2 4 10 0 1088 5 240 0 4 2 1068 4 272 8 3 6 1040 2 307 9 3 2 985 0 337 2 2 7 83...

Page 43: ...491 4 340 1 4 0 1465 7 384 4 3 5 1435 3 433 8 3 1 1379 2 480 1 2 7 1307 7 519 9 2 4 1260 5 504 6 2 4 10 0 1531 8 343 5 4 1 1505 1 387 5 3 6 1473 6 436 9 3 2 1412 8 481 9 2 8 1339 2 521 7 2 4 1272 3 49...

Page 44: ...1 7 2 7 528 8 211 3 2 3 520 3 215 1 2 3 9 0 623 5 133 4 4 2 613 9 150 7 3 7 602 3 170 4 3 3 581 3 192 4 2 8 541 5 211 8 2 4 532 8 215 7 2 3 10 0 640 4 134 6 4 3 630 5 151 8 3 8 618 5 171 4 3 3 596 0 1...

Page 45: ...2 4 666 7 264 0 2 4 9 0 798 4 168 8 4 3 785 1 191 0 3 8 769 8 217 5 3 3 743 7 245 5 2 8 693 1 261 0 2 5 682 6 263 7 2 4 10 0 820 2 170 7 4 3 806 4 192 3 3 8 790 5 218 4 3 3 762 5 245 6 2 9 709 5 260...

Page 46: ...58 7 347 9 2 3 9 0 1045 2 221 1 4 3 1027 4 250 9 3 7 1005 4 285 5 3 3 967 3 322 3 2 8 894 2 343 9 2 4 879 6 348 1 2 4 10 0 1073 8 223 4 4 4 1055 6 252 5 3 8 1033 0 286 9 3 3 991 0 322 2 2 9 915 8 344...

Page 47: ...EL YCIV0357E V AIR TEMPERATURE ON CONDENSER C LCWT C 25 0 30 0 35 0 40 0 45 0 46 0 KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP KW KW COP 5 0 1228 4 287 0 3 9 1206 7 325 4 3 4 1181 0 367 8 3 0 11...

Page 48: ...5 5 6 5 6 6 LOW NOISE FANS FAN MOTOR HP 2 2 2 2 2 2 2 TOTAL CHILLER AIRFLOW CFM 104000 104000 117000 117000 130000 143000 156000 ULTRA QUIET FANS FAN MOTOR HP 2 2 2 2 2 2 2 TOTAL CHILLER AIRFLOW CFM 1...

Page 49: ...CKT 1 CKT 2 5 4 4 5 4 4 5 5 6 6 6 6 6 6 3 3 LOW NOISE FANS FAN MOTOR HP KWI 2 1 8 2 1 8 2 1 8 2 1 8 2 1 8 TOTAL CHILLER AIRFLOW CFM 169000 182000 208000 234000 234000 ULTRA QUIET FANS FAN MOTOR HP KWI...

Page 50: ...2 2 2 2 2 2 2 TOTAL CHILLER AIRFLOW CFM 104000 117000 130000 130000 143000 156000 156000 ULTRA QUIET FANS FAN MOTOR HP 2 2 2 2 2 2 2 TOTAL CHILLER AIRFLOW CFM 104000 117000 130000 130000 143000 156000...

Page 51: ...FAN MOTOR HP KWI 2 1 8 2 1 8 2 1 8 2 1 8 TOTAL CHILLER AIRFLOW CFM 182000 208000 208000 234000 ULTRA QUIET FANS FAN MOTOR HP KWI 2 1 50 2 1 50 2 1 50 2 1 50 TOTAL CHILLER AIRFLOW CFM 182000 208000 20...

Page 52: ...I 2 1 50 2 1 50 2 1 50 2 1 50 2 1 50 2 1 50 2 1 50 TOTAL CHILLER AIRFLOW L SEC 49082 49082 55218 55218 61353 67488 73624 ULTRA QUIET FANS FAN MOTOR HP KWI 2 1 50 2 1 50 2 1 50 2 1 50 2 1 50 2 1 50 2 1...

Page 53: ...6 3 3 LOW NOISE FANS FAN MOTOR HP KWI 2 1 50 2 1 50 2 1 50 2 1 50 2 1 50 TOTAL CHILLER AIRFLOW L SEC 79768 85904 98176 110448 110448 ULTRA QUIET FANS FAN MOTOR HP KWI 2 1 50 2 1 50 2 1 50 2 1 50 2 1...

Page 54: ...1 50 2 1 50 TOTAL CHILLER AIRFLOW L SEC 49082 55218 61353 61353 67488 73624 73624 ULTRA QUIET FANS FAN MOTOR HP KWI 2 1 50 2 1 50 2 1 50 2 1 50 2 1 50 2 1 50 2 1 50 TOTAL CHILLER AIRFLOW L SEC 49082...

Page 55: ...5 05 06 06 06 06 LOW NOISE FANS FAN MOTOR HP KWI 2 1 50 2 1 50 2 1 50 2 1 50 TOTAL CHILLER AIRFLOW L SEC 85904 98176 98176 110448 ULTRA QUIET FANS FAN MOTOR HP KWI 2 1 50 2 1 50 2 1 50 2 1 50 TOTAL CH...

Page 56: ...hnson Controls unit controls will optimize the operation without nuisance high pressure safety cutouts however the system designer MUST consider potential performance degradation Access to the unit co...

Page 57: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 57...

Page 58: ...controls will optimize the operation without nuisance high pressure safety cutouts however the system designer MUST consider potential performance degradation Access to the unit control center stipul...

Page 59: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 59...

Page 60: ...diminished performance Johnson Controls unit controls will optimize the operation without nuisance high pressure safety cutouts however the system designer MUST consider potential performance degrada...

Page 61: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 61...

Page 62: ...g in unpre dictable air patters and possible diminished performance Johnson Controls unit controls will optimize the operation without nuisance high pressure safety cutouts however the system designer...

Page 63: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 63...

Page 64: ...sulting in unpre dictable air patters and possible diminished performance Johnson Controls unit controls will optimize the operation without nuisance high pressure safety cutouts however the system de...

Page 65: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 65...

Page 66: ...g in unpre dictable air patters and possible diminished performance Johnson Controls unit controls will optimize the operation without nuisance high pressure safety cutouts however the system designer...

Page 67: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 67...

Page 68: ...re dictable air patters and possible diminished performance Johnson Controls unit controls will optimize the operation without nuisance high pressure safety cutouts however the system designer MUST co...

Page 69: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 69...

Page 70: ...re dictable air patters and possible diminished performance Johnson Controls unit controls will optimize the operation without nuisance high pressure safety cutouts however the system designer MUST co...

Page 71: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 71...

Page 72: ...g in unpre dictable air patters and possible diminished performance Johnson Controls unit controls will optimize the operation without nuisance high pressure safety cutouts however the system designer...

Page 73: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 73...

Page 74: ...g in unpre dictable air patters and possible diminished performance Johnson Controls unit controls will optimize the operation without nuisance high pressure safety cutouts however the system designer...

Page 75: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 75...

Page 76: ...e dictable air patters and possible diminished performance Johnson Controls unit controls will optimize the operation without nuisance high pressure safety cutouts however the system designer MUST con...

Page 77: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 77...

Page 78: ...AL FIN COILS 1715 1579 1559 1274 774 CU FIN COILS 1715 1700 1898 1653 935 RS LS1 AL FIN COILS 1894 1757 1559 1274 774 RS LS1 CU FIN COILS 1894 1878 1898 1653 935 RIGHT R 9 1 1 3 59 4 1 3 109 4 1 3 19...

Page 79: ...2370 1470 RS LS1 CU FIN COILS 1951 1933 2297 2324 2714 1642 RIGHT R 9 1 1 3 58 1 1 3 111 1 1 3 204 7 1 3 284 9 1 3 368 1 3 AL FIN COILS 1753 1596 2540 2632 2897 1188 CU FIN COILS 1775 1768 2884 2978...

Page 80: ...L FIN COILS 1715 1581 1676 1287 820 CU FIN COILS 1715 1702 2015 1667 981 RS LS1 AL FIN COILS 1894 1759 1676 1287 820 RS LS1 CU FIN COILS 1894 1881 2015 1667 981 RIGHT R 9 1 1 3 59 4 1 3 109 4 1 3 195...

Page 81: ...6 RS LS1 CU FIN COILS 1951 1944 2751 2840 3166 1638 0287E V LEFT L 9 1 86 8 59 4 86 8 109 4 86 8 185 4 86 8 284 4 86 8 358 5 86 8 411 9 86 8 AL FIN COILS 1753 1585 1847 1870 1574 1049 928 CU FIN COILS...

Page 82: ...4 4970 2204 6740 2204 AL FIN COILS 778 716 707 578 351 CU FIN COILS 778 771 861 750 424 RS LS1 AL FIN COILS 859 797 707 578 351 RS LS1 CU FIN COILS 859 852 861 750 424 RIGHT R 230 32 1510 32 2780 32 4...

Page 83: ...LS1 CU FIN COILS 885 877 1042 1054 1231 745 RIGHT R 230 32 1475 32 2823 32 5199 32 7236 32 9346 32 AL FIN COILS 795 724 1152 1194 1314 539 CU FIN COILS 805 802 1308 1351 1470 607 RS LS1 AL FIN COILS...

Page 84: ...N COILS 778 772 914 756 445 RS LS1 AL FIN COILS 859 798 760 584 372 RS LS1 CU FIN COILS 859 853 914 756 445 RIGHT R 230 32 1510 32 2780 32 4970 32 6740 32 AL FIN COILS 770 708 708 584 372 CU FIN COILS...

Page 85: ...RS LS1 CU FIN COILS 885 882 1248 1288 1436 743 0287E V LEFT L 230 2204 1510 2204 2780 2204 4710 2204 7225 2204 9105 2204 10463 2204 AL FIN COILS 795 719 838 848 714 476 421 CU FIN COILS 805 786 967 10...

Page 86: ...156 464 THRU 524 CP 1D 1785N GRAY RED 1157 THRU 1785 525 THRU 810 MODEL NUMBER COLOR CODE RATED CAPACITY FOR UNITS WITH ANY LOAD POINT ABOVE 1518 LBS 689 KG LBS KG C2P 1D 1350 DARK PURPLE UP THRU 1148...

Page 87: ...W RD1 WR 3 13 1 75 1 25 2 38 0 34 0 19 5 16 18 UNC X 3 4 1 25 RD2 WR 3 88 2 38 1 75 3 00 0 34 0 22 3 8 16 UNC X 1 1 75 RD3 WR 5 50 3 38 2 88 4 13 0 56 0 25 1 2 13 UNC X 1 2 50 RD4 WR 6 25 4 63 2 75 5...

Page 88: ...60 GREEN UP THRU 391 UP TO 177 Y2RSI 2D 710 DARK BROWN 392 THRU 604 178 274 Y2RSI 2D 870 RED 605 THRU 740 275 336 Y2RSI 2D 1200N RED BLACK 741 THRU 1020 337 463 Y2RSI 2D 1690 PINK 1021 THRU 1437 464 6...

Page 89: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 89 INTENTIONALLY LEFT BLANK...

Page 90: ...60 205 5 3 5 205 5 9 3 0247 460 60 193 6 2 8 380 60 245 6 3 5 245 6 9 3 0267 460 60 191 6 2 8 380 60 242 6 3 5 242 6 9 3 YCIV S P CONTROL KVA 7 UNIT SHORT CIRCUIT WITH STAND KA FIELD WIRING PROTECTIO...

Page 91: ...152 4 3 5 152 4 9 3 162 4 2 8 206 4 3 5 206 4 9 3 162 5 2 8 205 5 3 5 205 5 9 3 160 5 2 8 203 5 3 5 203 5 9 3 191 6 2 8 242 6 3 5 242 6 9 3 HIGH HEAD HIGH STATIC FANS TWO SPEED COND FANS MINIMUM CKT...

Page 92: ...227 460 60 150 6 2 8 380 60 190 6 3 5 190 6 9 3 0247 460 60 194 6 2 8 380 60 245 6 3 5 245 6 9 3 YCIV E V CONTROL KVA 7 UNIT SHORT CIRCUIT WITHSTAND KA FIELD WIRING PROTECTION STD ULTRA QUIET COND FAN...

Page 93: ...32 5 3 5 132 5 9 3 141 5 2 8 179 5 3 5 179 5 9 3 152 5 2 8 193 5 3 5 193 5 9 3 150 6 2 8 190 6 3 5 190 6 9 3 149 6 2 8 188 6 3 5 188 6 9 3 HIGH HEAD HIGH STATIC FANS TWO SPEED COND FANS MINIMUM CKT AM...

Page 94: ...00 0397 2 4 30KA 65KA 671 800 800 800 2 4 30KA 65KA 847 1000 1000 1000 911 1000 0457 4 30KA 65KA N A N A N A N A 569 700 MODEL SYSTEM 1 SYSTEM 2 STD ULTRA QUIET COND FANS HIGH HEAD STATIC COND FANS TW...

Page 95: ...600 KCM 4 4 0 500 KCM 800 800 4 2 600 KCM 4 4 0 500 KCM 4 2 600 KCM 4 4 0 500 KCM 1000 1000 4 2 600 KCM 4 4 0 500 KCM 4 2 600 KCM 4 4 0 500 KCM 1000 1000 4 2 600 KCM 4 4 0 500 KCM 800 800 N A N A N A...

Page 96: ...152 5 2 8 152 5 2 8 380 60 193 5 3 5 193 5 9 3 193 5 3 5 0357 460 60 181 6 2 8 181 6 2 8 380 60 229 6 3 5 229 6 9 3 229 6 3 5 YCIV S P CONTROL KVA 7 UNIT SHORT CIRCUIT WITHSTAND KA FIELD WIRING PROTE...

Page 97: ...78 6 3 5 178 6 9 3 139 6 2 8 229 6 9 3 176 6 3 5 176 6 9 3 FIELD WIRING PROTECTION FIELD WIRING LUGS HIGH HEAD HIGH STATIC FANS TWO SPEED COND FANS STD TERMINAL BLOCK OPT CIRCUIT BREAKER MAX IN VERSE...

Page 98: ...ual point power 2 and 3 compressor units 2 Maximum Inverse Time Circuit Breaker or Dual Element Fuse 225 of the largest compressor RLA plus the sum of all other loads per NEC 440 22 A 3 MCA Minimum Ci...

Page 99: ...HNSON CONTROLS FORM 201 23 EG1 1013 99 FIG 1 TWO COMPRESSOR WIRING DIAGRAM WITH CIRCUIT BREAKER 2 COMPRESSOR POWER WIRING CONNECTIONS FIG 2 TWO COMPRESSOR WIRING DIAGRAM WITH TERMINAL BLOCK Power Wiri...

Page 100: ...TOR HEATER UNIT CONTROLS FIELD PROVIDED UNIT POWER SUPPLY VSD 1 VSD CONTROL PANEL LINE REACTOR VSD 3 VSD 2 CIRCUIT BREAKER GRD STANDARD CONTROL TRANSFORMER 3 COMPRESSOR POWER WIRING CONNECTIONS See No...

Page 101: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 101 FIG 7 FOUR COMPRESSOR WIRING DIAGRAM WITH CIRCUIT BREAKER MULTI POINT FIG 8 FOUR COMPRESSOR WIRING DIAGRAM WITH TERMINAL BLOCK MULTI POINT...

Page 102: ...JOHNSON CONTROLS 102 FORM 201 23 EG1 1013 Typical Control Wiring Two Compressor...

Page 103: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 103 For informational purposes only Do not attempt to tie into wiring without a proper wiring diagram...

Page 104: ...JOHNSON CONTROLS 104 FORM 201 23 EG1 1013 Typical Control Wiring Three Compressor...

Page 105: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 105 For informational purposes only Do not attempt to tie into wiring without a proper wiring diagram...

Page 106: ...JOHNSON CONTROLS 106 FORM 201 23 EG1 1013 Typical Control Wiring Four Compressor...

Page 107: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 107...

Page 108: ...roof at the spring isolator locations Ground Locations Units must be installed on a sub stantial base that will not settle and cause strain on the refrigerant lines resulting in possible leaks A one p...

Page 109: ...al of its manufacture against defects in workmanship and material for a period of eighteen 18 months from date of initial start up or date of availability 1 03 DELIVERY AND HANDLING A Unit shall be de...

Page 110: ...erload protection and external cur rent overload on all three phases C Lubrication External oil separators with no moving parts 450 psig design working pressure and UL listing are provided on the chil...

Page 111: ...ipment with power factor correction capacitors as required to maintain a displace ment power factor of 95 at all load conditions 2 The installing contractor is responsible for ad ditional cost to furn...

Page 112: ...e the following options as required to meet scheduled sound performance data at all load points a Normal speed fans and unlined compressor enclosure Factory Mounted b Two speed fans and acousticallly...

Page 113: ...ors 2 1 Inch Deflection Spring Isolators Level adjust able spring and cage type isolators for mounting under the unit base rails 3 2 Deflection Seismic Isolators Level adjust able restrained mounts in...

Page 114: ...Form 201 23 EG1 1013 Supersedes 201 23 EG1 713...

Reviews: