JOHNSON CONTROLS
52
FORM 201.23-EG1 (1013)
Physical Data (SI - Standard Efficiency)
REFRIGERANT R-134A
STANDARD EFFICIENCY
MODEL NUMBER (YCIV____ S/P)
GENERAL UNIT DATA
60HZ
0157
0177
0187
0207
0227
0247
0267
NUMBER OF INDEPENDENT REFRIGERANT CIRCUITS
2
2
2
2
2
2
2
REFRIGERANT CHARGE, R-134A, CKT.-1/CKT.-2, KG.
74/74
77/77
84/77
87/80
87/87
105/89
105/105
OIL CHARGE, CKT.-1/CKT.-2, LITERS
19/19
19/19
19/19
19/19
19/19
19/19
19/19
COMPRESSORS, SEMIHERMETIC SCREW QTY PER CHILLER
2
2
2
2
2
2
2
CONDENSERS, HIGH EFFICIENCY FIN/TUBE WITH INTEGRAL SUBCOOLER
TOTAL CHILLER COIL FACE AREA, M
2
21.8
21.8
24.5
24.5
27.2
30.0
32.7
NUMBER OF ROWS
3
3
3
3
3
3
3
FINS PER METER
669
669
669
669
669
669
669
CONDENSER FANS
NUMBER, CKT.-1/CKT.-2
4/4
4/4
5/4
5/4
5/5
6/5
6/6
LOW NOISE FANS
FAN MOTOR, HP/KWI
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
TOTAL CHILLER AIRFLOW, L/SEC.
49082
49082
55218
55218
61353
67488
73624
ULTRA QUIET FANS
FAN MOTOR, HP/KWI
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
TOTAL CHILLER AIRFLOW, L/SEC.
49082
49082
55218
55218
61353
67488
73624
D
UAL SPEED FANS - NORMAL SPEED
FAN, KWI
1.5
1.5
1.5
1.5
1.5
1.5
1.5
TOTAL CHILLER, M
3
/S
42
42
47
47
52
57
62
DUAL SPEED FANS - LOWER SPEED
FAN, KWI
1.5
1.5
1.5
1.5
1.5
1.5
1.5
TOTAL CHILLER, M
3
/S
32
32
36
36
40
44
48
HIGH STATIC FANS
FAN, KWI
3.7
3.7
3.7
3.7
3.7
3.7
3.7
TOTAL CHILLER, M
3
/S
49
49
55
55
61
67
74
EVAPORATOR, DIRECT EXPANSION
WATER VOLUME, LITERS
253.6
359.6
359.6
529.9
529.9
529.9
529.9
MAXIMUM WATER SIDE PRESSURE, BAR
1
10
10
10
10
10
10
10
MAXIMUM REFRIGERANT SIDE PRESSURE, BAR
16
16
16
16
16
16
16
MINIMUM CHILLED WATER FLOW RATE, L/SEC.
8.8
10.1
10.1
11.4
11.4
11.4
11.4
MAXIMUM CHILLED WATER FLOW RATE, L/SEC.
42.6
47.3
47.3
50.5
50.5
50.5
50.5
WATER CONNECTIONS, INCHES
8
10
10
10
10
10
10
Summary of Contents for YCIV0157E/V
Page 57: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 57...
Page 59: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 59...
Page 61: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 61...
Page 63: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 63...
Page 65: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 65...
Page 67: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 67...
Page 69: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 69...
Page 71: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 71...
Page 73: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 73...
Page 75: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 75...
Page 77: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 77...
Page 89: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 89 INTENTIONALLY LEFT BLANK...
Page 102: ...JOHNSON CONTROLS 102 FORM 201 23 EG1 1013 Typical Control Wiring Two Compressor...
Page 104: ...JOHNSON CONTROLS 104 FORM 201 23 EG1 1013 Typical Control Wiring Three Compressor...
Page 106: ...JOHNSON CONTROLS 106 FORM 201 23 EG1 1013 Typical Control Wiring Four Compressor...
Page 107: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 107...
Page 114: ...Form 201 23 EG1 1013 Supersedes 201 23 EG1 713...