MODEL: YCIV0207S/P
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25.0
30.0
35.0
40.0
45.0
46.0
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
5.0
689.5
170.6
3.7
676.6
196.8
3.2
662.1
226.0
2.8
629.2
248.2
2.4
564.5
248.2
2.1
530.0
233.3
2.1
6.0
709.0
171.7
3.8
695.5
197.6
3.3
680.0
226.6
2.8
644.2
248.0
2.5
569.7
242.9
2.2
536.2
228.8
2.2
7.0
728.8
173.0
3.9
714.8
198.5
3.4
697.4
226.7
2.9
659.6
247.8
2.5
576.2
238.0
2.3
542.0
223.9
2.3
8.0
749.1
174.4
4.0
734.4
199.5
3.4
715.2
226.8
3.0
675.3
247.4
2.6
582.3
232.8
2.4
547.6
219.0
2.3
9.0
769.7
176.1
4.0
754.5
200.6
3.5
733.3
227.1
3.0
691.2
247.0
2.6
588.4
227.7
2.4
553.1
214.3
2.4
10.0
790.7
178.1
4.1
774.9
202.0
3.6
751.7
227.4
3.1
707.2
246.7
2.7
594.3
222.6
2.5
558.1
209.8
2.5
11.0
812.1
180.2
4.2
795.7
203.6
3.6
770.3
227.8
3.2
723.6
246.3
2.8
599.9
217.8
2.6
563.0
205.4
2.6
12.0
834.0
182.6
4.2
816.9
205.3
3.7
789.3
228.2
3.2
740.2
245.9
2.8
605.2
213.2
2.7
567.7
200.9
2.6
13.0
856.2
185.1
4.3
838.5
207.2
3.8
808.6
228.9
3.3
757.1
245.6
2.9
610.1
208.7
2.7
572.5
196.6
2.7
MODEL: YCIV0227S/P
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25.0
30.0
35.0
40.0
45.0
46.0
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
5.0
748.4
182.6
3.8
735.1
208.5
3.3
720.1
236.9
2.8
690.4
263.0
2.5
640.3
275.7
2.2
630.5
278.0
2.1
6.0
769.6
184.0
3.8
755.7
209.7
3.3
739.9
238.2
2.9
707.1
263.1
2.5
655.5
276.0
2.2
645.2
278.3
2.2
7.0
791.1
185.5
3.9
776.7
211.0
3.4
760.1
239.6
3.0
724.0
263.2
2.6
671.0
276.2
2.3
660.4
278.6
2.2
8.0
813.1
187.2
4.0
798.1
212.4
3.5
780.9
241.0
3.0
741.2
263.3
2.7
686.8
276.3
2.3
676.0
278.7
2.3
9.0
835.5
189.0
4.1
819.9
214.1
3.6
802.0
242.4
3.1
758.8
263.3
2.7
702.9
276.4
2.4
690.9
278.2
2.3
10.0
858.4
190.9
4.1
842.2
215.7
3.6
823.6
244.0
3.2
776.3
263.4
2.8
719.2
276.5
2.5
697.1
272.2
2.4
11.0
881.7
193.0
4.2
864.9
217.5
3.7
845.6
245.6
3.2
794.4
263.5
2.8
735.9
276.4
2.5
703.5
266.0
2.5
12.0
905.3
195.2
4.3
888.1
219.4
3.8
867.9
247.4
3.3
812.7
263.6
2.9
752.5
276.2
2.6
710.1
259.7
2.6
13.0
929.1
197.6
4.3
911.5
221.4
3.8
890.8
249.3
3.4
831.3
263.7
3.0
759.3
269.5
2.7
716.0
253.0
2.7
MODEL: YCIV0247S/P
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25.0
30.0
35.0
40.0
45.0
46.0
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
KW
KW
COP
5.0
821.2
201.2
3.7
807.2
229.1
3.3
791.2
259.7
2.8
762.5
289.7
2.5
716.5
309.3
2.2
707.4
313.0
2.1
6.0
844.2
202.8
3.8
829.7
230.5
3.3
812.9
261.2
2.9
781.4
290.3
2.5
733.9
310.0
2.2
724.3
313.8
2.2
7.0
867.7
204.5
3.9
852.5
232.1
3.4
834.9
262.9
3.0
800.6
290.9
2.6
751.6
310.7
2.3
740.0
313.3
2.2
8.0
891.5
206.4
4.0
875.8
233.9
3.5
857.5
264.6
3.0
820.1
291.5
2.7
769.8
311.3
2.3
747.8
307.2
2.3
9.0
915.8
208.4
4.0
899.5
235.7
3.5
880.5
266.3
3.1
839.9
292.1
2.7
788.2
311.9
2.4
755.3
300.7
2.4
10.0
940.5
210.4
4.1
923.7
237.6
3.6
904.0
268.2
3.2
859.8
292.8
2.8
804.7
311.1
2.4
762.4
293.8
2.4
11.0
965.7
212.7
4.2
948.2
239.6
3.7
927.8
270.0
3.2
880.3
293.4
2.8
812.6
304.1
2.5
769.0
286.5
2.5
12.0
991.2
215.1
4.2
973.3
241.7
3.7
952.1
272.1
3.3
901.1
294.0
2.9
820.0
296.6
2.6
775.2
279.1
2.6
13.0
1017.2 217.0
4.3
998.6
243.9
3.8
976.9
274.2
3.3
922.2
294.7
2.9
826.9
289.0
2.7
780.9
272.0
2.7
NOTES:
1. kWo
= Unit kW Cooling Capacity Output
2. kW
i
= Compressor kW Input
3. COP
= Coefficient of Performance (includes condenser fan power)
4. LCWT = Leaving Chilled Water Temperature
5. Ratings based on 0.168 l/s cooler water per ton, and 0.018 (m
2
– °C)/kW
Summary of Contents for YCIV0177S/P
Page 57: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 57...
Page 59: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 59...
Page 61: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 61...
Page 63: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 63...
Page 65: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 65...
Page 67: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 67...
Page 69: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 69...
Page 71: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 71...
Page 73: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 73...
Page 75: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 75...
Page 77: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 77...
Page 89: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 89 INTENTIONALLY LEFT BLANK...
Page 102: ...JOHNSON CONTROLS 102 FORM 201 23 EG1 1013 Typical Control Wiring Two Compressor...
Page 104: ...JOHNSON CONTROLS 104 FORM 201 23 EG1 1013 Typical Control Wiring Three Compressor...
Page 106: ...JOHNSON CONTROLS 106 FORM 201 23 EG1 1013 Typical Control Wiring Four Compressor...
Page 107: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 107...
Page 114: ...Form 201 23 EG1 1013 Supersedes 201 23 EG1 713...