JOHNSON CONTROLS
90
FORM 201.23-EG1 (1013)
Electrical Data - 2 Comp Standard Efficiency
See page 138 for Electrical Data footnotes.
STANDARD EFFICIENCY YCIV_ _ _ _ S/P
STANDARD EFFICIENCY YCIV_ _ _ _ S/P
MODEL NO./NAMEPLATE
SYSTEM 1
SYSTEM 2
STD. & ULTRA QUIET COND.
FANS
HIGH HEAD/STATIC COND. FANS
TWO-SPEED COND. FANS
STD. & ULTRA QUIET COND. FANS
HIGH HEAD/STATIC COND. FANS
TWO-SPEED COND. FANS
YCIV S/P
INPUT
VOLTS (9)
INPUT
FREQ
COMPRES-
SOR
RLA (5)
CONDENSER FANS
COMPRES-
SOR
CONDENSER FANS
COMPRES-
SOR
RLA (5)
CONDENSER FANS
COMPRES-
SOR
RLA (5)
CONDENSER FANS
COMPRES-
SOR
RLA (5)
CONDENSER FANS
COMPRES-
SOR
RLA (5)
CONDENSER FANS
QTY.
FLA (EA)
RLA (5)
QTY.
FLA (EA)
QTY.
FLA (EA)
QTY.
FLA (EA)
QTY.
FLA (EA)
QTY.
FLA (EA)
0157
460
60
120
4
2.8
120
4
2.8
380
60
152
4
3.5
152
4
9.3
152
4
3.5
152
4
9.3
0177
460
60
159
4
2.8
105
4
2.8
380
60
201
4
3.5
201
4
9.3
133
4
3.5
133
4
9.3
0187
460
60
162
5
2.8
120
4
2.8
380
60
205
5
3.5
205
5
9.3
152
4
3.5
152
4
9.3
0207
460
60
145
5
2.8
162
4
2.8
380
60
184
5
3.5
184
5
9.3
206
4
3.5
206
4
9.3
0227
460
60
162
5
2.8
162
5
2.8
380
60
205
5
3.5
205
5
9.3
205
5
3.5
205
5
9.3
0247
460
60
193
6
2.8
160
5
2.8
380
60
245
6
3.5
245
6
9.3
203
5
3.5
203
5
9.3
0267
460
60
191
6
2.8
191
6
2.8
380
60
242
6
3.5
242
6
9.3
242
6
3.5
242
6
9.3
YCIV S/P
CONTROL
KVA (7)
UNIT SHORT CIRCUIT WITH-
STAND (KA)
FIELD WIRING & PROTECTION
STD. & ULTRA QUIET COND. FANS
HIGH HEAD/HIGH STATIC FANS
TWO-SPEED COND. FANS
TERMINAL
BLOCK (STD)
CIRCUIT
BREAKER (OPT)
MINIMUM CKT.
AMPACITY
(MCA) (3)
RECOMMENDED
FUSE/CKT.
BREAKER RAT-
ING (4)
MAX. INVERSE
TIME CKT.
BRKR. RATING
(2)
MAX DUAL
ELEMENT FUSE
SIZE (2)
MINIMUM CKT.
AMPACITY
(MCA) (3)
RECOMMENDED
FUSE/CKT.
BREAKER RAT-
ING (4)
MAX. INVERSE
TIME CKT.
BRKR. RATING
(2)
MAX DUAL
ELEMENT FUSE
SIZE (2)
MINIMUM CKT.
AMPACITY
(MCA) (3)
RECOMMENDED
FUSE/CKT.
BREAKER RAT-
ING (4)
MAX. INVERSE
TIME CKT.
BRKR. RATING
(2)
MAX DUAL
ELEMENT FUSE
SIZE (2)
0157
1.8
30KA
65KA
293
350
400
400
1.8
30KA
65KA
370
450
500
500
417
500
500
500
0177
1.8
30KA
65KA
326
400
450
450
1.8
30KA
65KA
413
500
600
600
459
600
600
600
0187
1.8
30KA
65KA
348
400
500
500
1.8
30KA
65KA
440
500
600
600
492
600
700
700
0207
1.8
30KA
65KA
373
450
500
500
1.8
30KA
65KA
472
600
600
600
525
600
700
700
0227
1.8
30KA
65KA
392
450
500
500
1.8
30KA
65KA
496
600
700
700
554
700
700
700
0247
1.8
30KA
65KA
433
500
600
600
1.8
30KA
65KA
547
700
700
700
610
700
800
800
0267
1.8
30KA
65KA
464
600
600
600
1.8
30KA
65KA
587
700
800
800
657
800
800
800
Summary of Contents for YCIV0177S/P
Page 57: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 57...
Page 59: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 59...
Page 61: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 61...
Page 63: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 63...
Page 65: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 65...
Page 67: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 67...
Page 69: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 69...
Page 71: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 71...
Page 73: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 73...
Page 75: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 75...
Page 77: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 77...
Page 89: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 89 INTENTIONALLY LEFT BLANK...
Page 102: ...JOHNSON CONTROLS 102 FORM 201 23 EG1 1013 Typical Control Wiring Two Compressor...
Page 104: ...JOHNSON CONTROLS 104 FORM 201 23 EG1 1013 Typical Control Wiring Three Compressor...
Page 106: ...JOHNSON CONTROLS 106 FORM 201 23 EG1 1013 Typical Control Wiring Four Compressor...
Page 107: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 107...
Page 114: ...Form 201 23 EG1 1013 Supersedes 201 23 EG1 713...