JOHNSON CONTROLS
FORM 201.23-EG1 (1013)
97
MODEL NO./NAMEPLATE
SYSTEM 1
SYSTEM 2
SYSTEM 2
SYSTEM 3
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC COND.
FANS
TWO-SPEED COND. FANS
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC COND.
FANS
TWO-SPEED COND. FANS
STD. & ULTRA QUIET
COND. FANS
HIGH HEAD/STATIC COND.
FANS
TWO-SPEED COND. FANS
YCIV E/V
INPUT
VOLTS
(9)
INPUT
FREQ
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CONDENSER
FANS
COMP.
CON-
DENSER
FANS
COMP.
CON-
DENSER
FANS
COMP.
CONDENSER
FANS
RLA (5)
QTY.
FLA (EA) RLA (5)
QTY.
FLA (EA) RLA (5)
QTY.
FLA (EA) RLA (5)
QTY.
FLA (EA)
RLA (5)
QTY.
FLA (EA) RLA (5)
QTY.
FLA (EA) RLA (5)
QTY.
FLA (EA) RLA (5)
QTY.
FLA (EA) RLA (5)
QTY.
FLA (EA)
0267
460
60
142
5
2.8
142
5
2.8
105
4
2.8
380
60
179
5
3.5
179
5
9.3
179
4
3.5
179
4
9.3
133
4
3.5
133
4
9.3
0287
460
60
137
5
2.8
137
5
2.8
137
5
2.8
380
60
173
5
3.5
173
5
9.3
173
5
3.5
173
5
9.3
173
4
3.5
173
4
9.3
0327
460
60
152
5
2.8
152
5
2.8
141
6
2.8
380
60
193
5
3.5
193
5
9.3
193
5
3.5
193
5
9.3
178
6
3.5
178
6
9.3
0357
460
60
181
6
2.8
181
6
2.8
139
6
2.8
380
60
229
6
3.5
229
6
9.3
229
6
3.5
229
6
9.3
176
6
3.5
176
6
9.3
YCIV S/P
CONTROL
KVA (7)
UNIT SHORT CIRCUIT
WITHSTAND (KA)
FIELD WIRING & PROTECTION
FIELD WIRING & PROTECTION
FIELD WIRING LUGS
STD. & ULTRA QUIET COND. FANS
HIGH HEAD/HIGH STATIC
FANS
HIGH HEAD/HIGH STATIC
FANS
TWO-SPEED COND. FANS
STD TERMINAL BLOCK
OPT CIRCUIT BREAKER
TERMINAL
BLOCK
(STD)
CIRCUIT
BREAKER
(OPT)
MINIMUM
CKT. AMPAC-
ITY (MCA) (3)
RECOM-
MENDED
FUSE/CKT.
BREAKER
RATING (4)
MAX. IN-
VERSE TIME
CKT. BRKR.
RATING (2)
MAX DUAL
ELEMENT
FUSE SIZE
(2)
MINIMUM
CKT. AMPAC-
ITY (MCA) (3)
RECOM-
MENDED
FUSE/CKT.
BREAKER
RATING (4)
MAX. IN-
VERSE TIME
CKT. BRKR.
RATING (2)
MAX DUAL
ELEMENT
FUSE SIZE
(2)
MINIMUM
CKT. AMPAC-
ITY (MCA) (3)
RECOM-
MENDED
FUSE/CKT.
BREAKER
RATING (4)
MAX. IN-
VERSE TIME
CKT. BRKR.
RATING (2)
MAX DUAL
ELEMENT
FUSE SIZE
(2)
LUGS/
PHASE
(1)
LUG WIRE
RANGE
LUGS/
PHASE
(1)
LUG WIRE
RANGE
0287
2.4
30KA
65KA
463
600
600
600
4
#2 - 600 KCM
4
#4/0 - 500 KCM
2.4
30KA
65KA
581
700
700
700
632
800
800
800
4
#2 - 600 KCM
4
#2 - 600 KCM
0307
2.4
30KA
65KA
486
600
600
600
4
#2 - 600 KCM
4
#2 - 600 KCM
2.4
30KA
65KA
610
700
700
700
659
800
800
800
4
#2 - 600 KCM
4
#2 - 600 KCM
0357
2.4
30KA
65KA
528
600
600
600
4
#2 - 600 KCM
4
#2 - 600 KCM
2.4
30KA
65KA
667
800
800
800
728
800
800
800
4
#2 - 600 KCM
4
#2 - 600 KCM
0397
2.4
30KA
65KA
598
700
700
700
4
#2 - 600 KCM
4
#2 - 600 KCM
2.4
30KA
65KA
755
800
800
800
818
1000
1000
1000
4
#2 - 600 KCM
4
#2 - 600 KCM
Summary of Contents for YCIV0177S/P
Page 57: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 57...
Page 59: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 59...
Page 61: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 61...
Page 63: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 63...
Page 65: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 65...
Page 67: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 67...
Page 69: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 69...
Page 71: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 71...
Page 73: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 73...
Page 75: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 75...
Page 77: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 77...
Page 89: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 89 INTENTIONALLY LEFT BLANK...
Page 102: ...JOHNSON CONTROLS 102 FORM 201 23 EG1 1013 Typical Control Wiring Two Compressor...
Page 104: ...JOHNSON CONTROLS 104 FORM 201 23 EG1 1013 Typical Control Wiring Three Compressor...
Page 106: ...JOHNSON CONTROLS 106 FORM 201 23 EG1 1013 Typical Control Wiring Four Compressor...
Page 107: ...JOHNSON CONTROLS FORM 201 23 EG1 1013 107...
Page 114: ...Form 201 23 EG1 1013 Supersedes 201 23 EG1 713...