7 STAGE
STEP
0: Both Compressors OFF
1: Lead Compr Unloaded, Lag Compr OFF
*2: Lead Compr 1 Stage Loading, Lag Compr OFF
*3: Lead Compr 1 Stage Loading, Lag Compr OFF
4: Lead Compr 2 Stages Loading, Lag Compr OFF
5: Lead Compr 1 Stage Loading,
Lag Compr Unloaded
*6: Lead Compr 1 Stage Loading,
Lag Compr 1 Stage Loading
*7: Lead Compr 1 Stage Loading,
Lag Compr 1 Stage Loading
*8: Lead Compr 1 Stage Loading,
Lag Compr 1 Stage Loading
9: Lead Compr 2 Stages Loading,
Lag Compr 1 Stage Loading
10: Lead Compr 2 Stages Loading,
Lag Compr 2 Stages Loading
10 STAGE
STEP
0: Both Compressors OFF
1: Lead Compr Unloaded, Lag Compr OFF
2: Lead Compr 1 Stage Loading, Lag Compr OFF
3: Lead Compr 2 Stages Loading, Lag Compr OFF
4: Lead Compr 3 Stages Loading, Lag Compr OFF
5: Lead Compr 2 Stages Loading,
Lag Compr Unloaded
6: Lead Compr 1 Stage Loading,
Lag Compr 1 Stage Loading
7: Lead Compr 2 Stages Loading,
Lag Compr 1 Stage Loading
8: Lead Compr 2 Stages Loading,
Lag Compr 2 Stages Loading
9: Lead Compr 3 Stages Loading,
Lag Compr 2 Stages Loading
10: Lead Compr 3 Stages Loading,
Lag Compr 3 Stages Loading
This message provides a real time display of the aver-
age rate of change of leaving chilled water as seen by
the micro. A (-) or (+) sign is also shown to indicate a
temperature fall or a temperature rise.
The Run Time for SYS 2 since the last start is displayed.
This message provides a real time display of the time
left on the Load Timer. The Load Timer is a constantly
recycling timer that the micro utilizes in conjunction with
rate control and temperature deviation from setpoint
to determine when loading should occur.
This message provides a real time display of the time
left on the Unload Timer. The Unload Timer is a con-
stantly recycling timer that the micro utilizes in conjunc-
tion with rate control and temperature deviation from
setpoint to determine when unloading should occur.
This message informs the operator what stage of load-
ing the chiller system is presently on as a result of com-
mands from the microprocessor. This is a coded number
and the steps must be decoded to be meaningful. The
decoding varies according to the number of stages pro-
grammed (Page 54). Tables for decoding the display mes-
sage are shown below:
5 STAGE
STEP
0: Both Compressors OFF
*1: Lead Compr Unloaded, Lag Compr OFF
*2: Lead Compr Unloaded, Lag Compr OFF
*3: Lead Compr Loaded, Lag Compr OFF
*4: Lead Compr Loaded, Lag Compr OFF
*5: Lead Compr Unloaded, Lag Compr Unloaded
*6: Lead Compr Unloaded, Lag Compr Unloaded
*7: Lead Compr Loaded, Lag Compr Unloaded
*8: Lead Compr Loaded, Lag Compr Unloaded
*9: Lead Compr Loaded, Lag Compr Loaded
*10: Lead Compr Loaded, Lag Compr Loaded
* On some STEPS, actual Loading will NOT change.
S Y S
2
R U N
T I M E
0
S E C S
L O A D
T I M E R
1 4 0
S E C S
U N L O A D
T I M E R
1 2 2
S E C S
T E M P E R A T U R E
D E M A N D
4
T E M P E R A T U R E
R A T E
1 . 5
D E G F / M I N
Summary of Contents for YCRJ45E00
Page 29: ...FORM 150 24 NM27 YORK INTERNATIONAL 29 CONTROL CIRCUIT With I O Expansion Board LD02106 ...
Page 30: ...30 YORK INTERNATIONAL FIG 9 SYSTEM WIRING ...
Page 31: ...FORM 150 24 NM27 YORK INTERNATIONAL 31 LD02678 ...
Page 35: ...FORM 150 24 NM27 YORK INTERNATIONAL 35 LD02679 ...
Page 36: ...36 YORK INTERNATIONAL MICROPANEL CONNECTION DIAGRAM With I O Expansion Board LD02107 ...
Page 37: ...FORM 150 24 NM27 YORK INTERNATIONAL 37 LD02108 ...