SECTION 9 – SERVICE AND TROUBLESHOOTING
FORM 201.26-NM1
ISSUE DATE: 1/19/2018
JOHNSON CONTROLS
161
9
Analog Inputs – Pressure
Refer to the unit wiring diagrams,
. Pressure inputs are connected
to the microboard on plugs J7 and J9. These
analog
inputs represent varying DC signals corresponding to
varying pressures. All voltages are in reference to the
unit case (ground).
System 1 discharge and suction pressures will be con-
nected to J7 of the microboard. System 2 discharge and
suction pressure transducers will be connected to J9 of
the microboard.
The discharge transducers are standard on all units.
If the discharge transducers are not installed, no con-
nections are made to the microboard and the discharge
pressure readout on the display would be zero.
The suction pressure transducers are standard on all
YCWL’s. The suction pressure transducers have a
range of 0 to 400 PSIG. The output will be linear from
0.5VDC to 4.5VDC over the 400 PSIG (27.5 barg)
range.
The discharge transducers have a range from 0 to
650 PSIG. The output will be linear from 0.5VDC to
4.5VDC over the 650 PSIG (41.25 barg) range. Fol-
lowing is the formula that can be used to verify the
voltage output of the transducer. All voltage readings
are in reference to ground (unit case).
TABLE 23 -
PRESSURE TRANSDUCERS
0-400 PSIG SUCTION
PRESSURE
TRANSDUCER
0-650 PSIG DISCHARGE
PRESSURE
TRANSDUCER
PRESSURE
PSIG
VOLTAGE
VDC
PRESSURE
PSIG
VOLTAGE
VDC
0
0.5
0
0.5
50
1.0
81.25
1.0
100
1.5
162.5
1.5
150
2.0
243.75
2.0
200
2.5
325
2.5
250
3.0
406.25
3.0
300
3.5
487.75
3.5
350
4.0
568.75
4.0
400
4.5
650
4.5
Red Wire = 5V, Black wire = 0V, White/Green Wire = signal
TEST POINTS:
Suction Pressure:
System 1: ...............................................Microboard J7-10 to J7-9
System 2: ...............................................Microboard J9-10 to J9-9
Discharge Pressure:
System 1: ...............................................Microboard J7-11 to J7-7
System 2: ...............................................Microboard J9-11 to J9-7
V = (Pressure in PSIG x .01) + .5
or
V = (Pressure in barg x .145) + .5
where V = DC voltage output
Pressure = pressure sensed by transducer
The I/O board connections for the Discharge
Transducers:
System 1 Discharge Transducer
J7-6 = +5VDC regulated supply to transducer.
J7-11 = VDC input signal to the microboard.
See the
formula above for voltage readings that cor-
respond to specific discharge pressures.
J7-7 = +5VDC return.
J7-2 = drain (shield connection = 0VDC).
System 2 Discharge Transducer
J9-6 = +5VDC regulated supply to transducer.
J9-11 = VDC input signal to the microboard.
See the
formula above for voltage readings that cor-
respond to specific discharge pressures.
J9-7 = +5VDC return.
J9-2 = drain (shield connection = 0VDC).
Summary of Contents for YCWL0056SE
Page 4: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 30 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 146: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 146 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 154: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 154 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 168: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 168 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 186: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 186 NOTES...