SECTION 5 – TECHNICAL DATA
FORM 201.26-NM1
ISSUE DATE: 1/19/2018
JOHNSON CONTROLS
61
5
WITH EXTERNAL COMPRESSOR OVERLOADS
VOLT HZ
SYSTEM # 1
SYSTEM # 2
QTY./
Ø
CIRCUIT
BREAKER
LUG
SIZES
COMPR 1 COMPR 2 COMPR 3
QTY./
Ø
CIRCUIT
BREAKER
LUG
SIZES
COMPR 1 COMPR 2 COMPR 3
RLA LRA RLA LRA RLA LRA
RLA LRA RLA LRA RLA LRA
208 60
(1) #6 - 350KCMIL 42.2 425 42.2 425 42.2 425
(1) #6 - 350KCMIL 42.2 425 42.2 425 42.2 425
230 60
(1) #6 - 350KCMIL 42.2 425 42.2 425 42.2 425
(1) #6 - 350KCMIL 42.2 425 42.2 425 42.2 425
380 60
(1)
#14 - 1/0AWG 25.7 239 25.7 239 25.7 239
(1)
#14 - 1/0AWG 25.7 239 25.7 239 25.7 239
460 60
(1)
#14 - 1/0AWG 21.3 187 21.3 187 21.3 187
(1)
#14 - 1/0AWG 21.3 187 21.3 187 21.3 187
575 60
(1)
#14 - 1/0AWG 17.4 148 17.4 148 17.4 148
(1)
#14 - 1/0AWG 17.4 148 17.4 148 17.4 148
208 60
(1) #6 - 350KCMIL 49.1 505 49.1 505 49.1 505
(1) #6 - 350KCMIL 49.1 505 49.1 505 49.1 505
230 60
(1) #6 - 350KCMIL 49.1 505 49.1 505 49.1 505
(1) #6 - 350KCMIL 49.1 505 49.1 505 49.1 505
380 60
(1)
#14 - 1/0AWG 28.3 290 28.3 290 28.3 290
(1)
#14 - 1/0AWG 28.3 290 28.3 290 28.3 290
460 60
(1)
#14 - 1/0AWG 23.4 225 23.4 225 23.4 225
(1)
#14 - 1/0AWG 23.4 225 23.4 225 23.4 225
575 60
(1)
#14 - 1/0AWG 18.7 180 18.7 180 18.7 180
(1)
#14 - 1/0AWG 18.7 180 18.7 180 18.7 180
208 60
(1) #6 - 350KCMIL 51.1 505 51.1 505 51.1 505
(1) #6 - 350KCMIL 79.0 599 79.0 599
–
–
230 60
(1) #6 - 350KCMIL 49.1 505 49.1 505 49.1 505
(1) #6 - 350KCMIL 79.0 599 79.0 599
–
–
380 60
(1)
#14 - 1/0AWG 28.3 290 28.3 290 28.3 290
(1)
#2 - 4/0AWG 45.5 358 45.5 358
–
–
460 60
(1)
#14 - 1/0AWG 23.4 225 23.4 225 23.4 225
(1)
#14 - 1/0AWG 37.6 310 37.6 310
–
–
575 60
(1)
#14 - 1/0AWG 18.7 180 18.7 180 18.7 180
(1)
#14 - 1/0AWG 30.1 239 30.1 239
–
–
208 60
(1) #6 - 350KCMIL 57.8 500 57.8 500 57.8 500
(1) #6 - 350KCMIL 57.8 500 57.8 500 57.8 500
230 60
(1) #6 - 350KCMIL 57.8 500 57.8 500 57.8 500
(1) #6 - 350KCMIL 57.8 500 57.8 500 57.8 500
380 60
(1)
#2 - 4/0AWG 33.3 305 33.3 305 33.3 305
(1)
#2 - 4/0AWG 33.3 305 33.3 305 33.3 305
460 60
(1)
#14 - 1/0AWG 27.5 250 27.5 250 27.5 250
(1)
#14 - 1/0AWG 27.5 250 27.5 250 27.5 250
575 60
(1)
#14 - 1/0AWG 22.0 198 22.0 198 22.0 198
(1)
#14 - 1/0AWG 22.0 198 22.0 198 22.0 198
208 60
(1) # 250 - 500 KCM 90.5 599 90.5 599
–
–
(1)
# 4 - 300 KCM 90.5 599 90.5 599
–
–
230 60
(1) # 250 - 500 KCM 78.7 599 78.7 599
–
–
(1)
# 4 - 300 KCM 78.7 599 78.7 599
–
–
380 60
(1)
#2 - 4/0AWG 47.7 358 47.7 358
–
–
(1)
#2 - 4/0AWG 47.7 358 47.7 358
–
–
460 60
(1)
#2 - 4/0AWG 39.4 310 39.4 310
–
–
(1)
#14 - 1/0AWG 39.4 310 39.4 310
–
–
575 60
(1)
#14 - 1/0AWG 31.5 239 31.5 239
–
–
(1)
#14 - 1/0AWG 31.5 239 31.5 239
–
–
DUAL POINT ELECTRICAL DATA (CONT’D)
Summary of Contents for YCWL0056SE
Page 4: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 30 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 146: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 146 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 154: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 154 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 168: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 168 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 186: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 186 NOTES...