FORM 201.26-NM1
ISSUE DATE: 1/19/2018
SECTION 5 – TECHNICAL DATA
JOHNSON CONTROLS
66
GROUND WIRE SIZING
GROUND LUG SIZING WITH OR WITHOUT OPTIONAL OVERLOADS
NON FUSED DISCONNECT SWITCH OPTION
RATING
INCOMING WIRE
GROUND WIRE
150A
# 14 - 1/0 AWG
# 8 - 2 AWG
150A
# 2 - 4/0 AWG
# 8 - 2 AWG
150A
# 4 - 300 KCM
# 8 - 2 AWG
225A
# 4 - 300 KCM
# 6 - 1/0 AWG
250A
# 6 - 350 KCM
# 4 - 3/0 AWG
400A
# 250 - 500 KCM
# 2 - 4/0 AWG
400A
(2) # 3/0 - 250 KCM
(2) # 6 - 1/0 AWG
600A
(2) # 250 - 500 KCM
(2) # 2 - 4/0 AWG
800A
(2) # 250 - 500 KCM
(2) # 2 - 4/0 AWG
800A
(3) # 2/0 - 400 KCM
(3) # 4 - 3/0 AWG
CIRCUIT BREAKER OPTION
RATING
INCOMING WIRE
GROUND WIRE
60A
# 14 - 1/0 AWG
# 14 - 6 AWG
70A
# 14 - 1/0 AWG
# 14 - 6 AWG
80A
# 14 - 1/0 AWG
# 14 - 6 AWG
90A
# 14 - 1/0 AWG
# 14 - 6 AWG
100A
# 14 - 1/0 AWG
# 8 - 2 AWG
125A
# 14 - 1/0 AWG
# 8 - 2 AWG
125A
# 2 - 4/0 AWG
# 8 - 2 AWG
150A
# 2 - 4/0 AWG
# 8 - 2 AWG
175A
# 4 - 300 KCM
# 6 - 1/0 AWG
200A
# 4 - 300 KCM
# 6 - 1/0 AWG
225A
# 4 - 300 KCM
# 6 - 1/0 AWG
250A
# 6 - 350 KCM
# 4 - 3/0 AWG
400A
# 250 - 500 KCM
# 2 - 4/0 AWG
400A
(2) # 3/0 - 250 KCM
(2) # 6 - 1/0 AWG
600A
(2) # 250 - 500 KCM
(2) # 2 - 4/0 AWG
TERMINAL BLOCK OPTION
RATING
INCOMING WIRE
GROUND WIRE
130A
# 12 - 1 AWG
# 8 - 2 AWG
165A
# 10 - 3/0 AWG
# 6 - 1/0 AWG
240A
# 10 - 300 KCM
# 4 - 3/0 AWG
320A
# 4 - 500 KCM
# 2 - 4/0 AWG
480A
(2) # 10 - 300 KCM
(2) # 4 - 3/0 AWG
Instructions:
1) Start in correct power option table (switch, breaker, terminal block)
2) Match engineering guide value for amperage
3) Match engineering guide value for wire range
4) Note corresponding ground wire range
Summary of Contents for YCWL0056SE
Page 4: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 30 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 146: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 146 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 154: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 154 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 168: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 168 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 186: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 186 NOTES...