SECTION 5 – TECHNICAL DATA
JOHNSON CONTROLS
86
FIGURE 33 -
ELEMENTARY WIRING DIAGRAM DETAILS, 5 AND 6 COMPRESSOR
ELEMENTARY WIRING DIAGRAM DETAILS
YCWL0104, 0118, 0156, 0177 and 0198 STANDARD EFFICIENCY UNITS
YCWL0096, 0126 and 0156 HIGH EFFICIENCY UNITS
035-21499-103 REV D
Notes:
1. Field wiring to be in accordance with the current edition of the National Electrical Code as well as all other applicable codes and specifi
cations.
2. Contacts must be suitable for switching 24VDC, (gold contacts recommended).Wiring shall not be run in the same conduit with any line
voltage (class 1) wiring.
3. To cycle unit ON and OFF automatically with contact shown, install a cycling device in series with the flow switch.
See note 2 for contact
rating and wiring specifications.
4. To stop unit (emergency stop) with contacts other than those shown, install the stop contact between terminals 5 and 1. If a stop device
is not installed, a jumper must be connected between terminals 5 and 1. Device must have a minimum contact rating of 6A at 115VAC.
5. Contacts are rated at 115V, 100VA, resistive load only, and must be suppressed at load by user.
6. Optional current readout. 5V = 200A.
7. 1MP thru 6MP are contained in their respective compressor junction boxes.
Summary of Contents for YCWL0056SE
Page 4: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 4 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 30: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 30 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 146: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 146 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 154: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 154 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 168: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 168 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 186: ...FORM 201 26 NM1 ISSUE DATE 1 19 2018 JOHNSON CONTROLS 186 NOTES...