YORK INTERNATIONAL
82
Maintenance
STANDARD UNITS
SERVICE SCHEDULE
MINOR SERVICE
MAJOR SERVICE
All items under Minor Service plus:
Unit general:
Check thermal insulation.
Check main structure.
Check vibration isolators.
Check paint-work.
Refrigerant systems
Check relief valves.
Check solenoid valves.
general:
Check fusible plugs.
Check for pipework damage.
Check for leaks.
Check moisture indicator.
Check suction superheat.
Check liquid subcooling.
Compressors /
Check oil level.
Oil separator:
Check oil pressure.
Check unloader operation.
Check crankcase heater.
Check condition of oil.
Cooler:
Check water flow.
Check water pH / glycol strength.
Check water pressure drop.
Condenser:
Check water flow.
Check water pH / glycol strength.
Check water pressure drop.
Power & Control
Check panel condition.
Check all connections.
system general:
Check mains and control wiring.
Check compressor contactors.
Check sensor locations.
Check sensor / transducer calibration.
Check mechanical HP cutouts.
Check motor protectors.
Check emergency stop.
Check contactor contacts.
Microprocessor
Check fault history.
Check low and high ambient cutout functions.
controls:
Check program settings.
Check low LCHLT cutout function.
Check HP / LP cutout functions.
Check low differential oil pressure function.
Check pump-down function.
Check low evaporator temperature cutout function.
Check load / unload function.
TABLE 7 – STANDARD UNITS
Summary of Contents for YCWS0313SC
Page 12: ...YORK INTERNATIONAL 12 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT...
Page 36: ...YORK INTERNATIONAL 36 THIS PAGE INTENTIONALLY LEFT BLANK TO MAINTAIN PAGE FORMAT Commissioning...
Page 86: ...YORK INTERNATIONAL 86 TYPICAL CONTROL PANEL WIRING Maintenance...
Page 87: ...FORM 201 24 NM2 87 YORK INTERNATIONAL TYPICAL CONTROL PANEL WIRING LD06957 8...
Page 103: ...FORM 201 24 NM2 103 YORK INTERNATIONAL NOTES 11...