Table 84: Programmable
Button
Access level
Description
Local leaving
chilled liquid
temperature -
setpoint
Operator
This value allows the user to define the Leaving Chilled Liquid Temperature that is to
be maintained by the chiller. It is programmable over the range of 38.0°F to 70.0°F
(water) or 10.0°F to 70.0°F (brine).
If Smart Freeze is enabled, the range is 36.0°F to 70.0°F (water). A remote device
can provide an analog signal (0-20 mA, 4-20 mA, 0-10 VDC or 2-10 VDC) in Analog
Remote mode, or PWM signal in Digital Remote mode that changes the setpoint
by creating an offset above the operator programmed Local Leaving Chilled Liquid
Temperature setpoint. This offset may be defined between 10.0°F and 40.0°F above
the Local setpoint (see the Remote Leaving Chilled Liquid Temperature Setpoint Range
description). Additionally, an SC-EQ in ISN (BAS) Remote mode can define the setpoint
through a serial data stream. In this case, the incoming setpoint is not an offset that
is applied to the locally programmed setpoint value, but rather is the setpoint value
itself.
Local leaving
chilled liquid
temperature -
range
Operator
This is the range over which an analog signal (0-20 mA, 4-20 mA, 0-10 VDC or 2-10 VDC)
in Analog Remote Mode or a digital signal (PWM) in Digital remote mode can reset the
Leaving Chilled Liquid Temperature setpoint above the operator programmed Base
Setpoint (see below). Programmable between 10°F and 40°F, with a default of 10°F, it
is added to the Local Setpoint value to create a range over which the remote device
can reset the setpoint. For example, if this setpoint is programmed for 10°F and the
operator programmed Local value is 45°F, then the remote device can set the Leaving
Chilled Liquid Temperature setpoint over the range 45.0°F - 55.0°F.
Leaving
chilled liquid
temperature
cycling offset -
shutdown
Operator
This value allows the user to specify the Leaving Chilled Liquid Temperature at which
the chiller will shut down on a LEAVING CHILLED LIQUID – LOW TEMPERATURE
cycling shutdown. This is done by defining an offset below the Leaving Chilled
Liquid Temperature setpoint. It is programmable over a range of 1°F to 70°F below
the setpoint, to a minimum cutout of 36°F (water) or 6°F (brine). It establishes the
minimum allowed temperature for the Leaving Chilled Liquid Temperature and
prevents overcooling of the building. When the Leaving Chilled Liquid Temperature
setpoint is increased, the shutdown threshold is ramped from the current setpoint
to the new setpoint at the rate of 0.1°F per second to prevent the chiller from
immediately tripping on low water temperature.
Leaving
chilled liquid
temperature
cycling offset -
restart
Operator
This value allows the user to specify the Leaving Chilled Liquid Temperature at
which the chiller will restart after a shutdown on a LEAVING CHILLED LIQUID – LOW
TEMPERATURE cycling shutdown. This is done by defining an offset above the Leaving
Chilled Liquid Temperature setpoint. It is programmable over a range of 0°F to X°F
where X = 80 minus the LCHLT Setpoint. The chiller will automatically restart when this
temperature is reached. This setpoint can be used to reduce chiller cycling by delaying
the chiller restart until the cooling load has increased.
Local chiller
current limit
Operator
Allows the user to specify the maximum allowed Chiller Current while running.
Adjustable between 30% and 100%; default = 100%.
Lead compressor
pulldown
demand limit
Operator
Allows the user to specify the maximum allowed Chiller Current during the Lead
Compressor Chiller Pulldown Period. The Chiller Pulldown Period is in effect from the
instant the chiller enters “System Run” until the Leaving Chilled liquid temperature is
within 2ºF of the Leaving Chilled Liquid Temperature Setpoint or the Lead Compressor
Pulldown Time has expired. Adjustable between 30% and 100%; default = 100%.
Lead compressor
pulldown time
Operator
Allows the user to specify the amount of time that the Lead Compressor Pulldown
Demand Limit will be in effect. Adjustable between 0 and 255 minutes; default = 0
minutes.
Remote analog
input range
Operator
Defines the remote signal range applied for remote reset of the Leaving Chilled Liquid
temperature Setpoint and Current Limit Setpoint in ANALOG remote mode. If the
remote signal is 0-10 VDC or 0-20 mA, this setpoint must be programmed for 0-10 VDC.
If the remote signal is 2-10 VDC or 4-20 mA, this setpoint must be programmed for
2-10 VDC.
View
Prints the Setpoints report.
Model YD Mod D with OptiView Control Center
94
Summary of Contents for YD Mod D
Page 2: ...2 Model YD Mod D with OptiView Control Center...
Page 8: ...Nomenclature Model YD Mod D with OptiView Control Center 8...
Page 17: ...Figure 2 Chiller operation flow chart 17 Model YD Mod D with OptiView Control Center...
Page 18: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 18...
Page 19: ...Figure 2 Chiller operation flow chart 19 Model YD Mod D with OptiView Control Center...
Page 20: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 20...
Page 21: ...Figure 2 Chiller operation flow chart 21 Model YD Mod D with OptiView Control Center...
Page 22: ...Figure 2 Chiller operation flow chart Model YD Mod D with OptiView Control Center 22...
Page 150: ...Figure 57 Sample printout status Model YD Mod D with OptiView Control Center 150...
Page 151: ...Figure 57 Sample printout status 151 Model YD Mod D with OptiView Control Center...
Page 152: ...Figure 58 Sample printout setpoints Model YD Mod D with OptiView Control Center 152...
Page 153: ...Figure 58 Sample printout setpoints 153 Model YD Mod D with OptiView Control Center...
Page 154: ...Figure 59 Sample printout schedule Model YD Mod D with OptiView Control Center 154...
Page 155: ...Figure 60 Sample printout sales order 155 Model YD Mod D with OptiView Control Center...
Page 156: ...Figure 61 Sample printout history Model YD Mod D with OptiView Control Center 156...
Page 157: ...Figure 61 Sample printout history 157 Model YD Mod D with OptiView Control Center...
Page 159: ...Figure 64 Sample printout custom screen report 159 Model YD Mod D with OptiView Control Center...