JOHNSON CONTROLS
120
FORM 160.69-O1
ISSUE DATE: 9/30/2012
SECTION 2 – OPTIVIEW CONTROL CENTER
“WARNING – COMPRESSOR #1 LOCKED
OUT”
Compressor #1 is inhibited from starting because it has
been placed in service lockout. This is performed on
the Compressor Capacity Cycling Screen.
“WARNING – COMPRESSOR #2 LOCKED
OUT”
Compressor #2 is inhibited from starting because it has
been placed in service lockout. This is performed on
the Compressor Capacity Cycling Screen.
“WARNING – OIL PUMP #1 – SEAL LUBRICA-
TION - LOW PRESSURE”
A minimum of 15 PSID of oil pressure was not achieved
in the first 30 seconds of the seal lubrication cycle (or
it dropped below this value during the remaining 90
seconds of the cycle) for compressor #1. This message
must be manually cleared using the WARNING RE-
SET key in Service access level (or higher). As soon as
the message is cleared, another seal lubrication will be
attempted. The message will also be cleared if Standby
Lube #1 is disabled on OIL PUMP 1 Screen or com-
pressor #1 enters the prelube state.
“WARNING – OIL PUMP #2 – SEAL LUBRICA-
TION - LOW PRESSURE”
A minimum of 15 PSID of oil pressure was not achieved
in the first 30 seconds of the seal lubrication cycle (or
it dropped below this value during the remaining 90
seconds of the cycle) for compressor #2. This message
must be manually cleared using the WARNING RE-
SET key in Service access level (or higher). As soon as
the message is cleared, another seal lubrication will be
attempted. The message will also be cleared if Standby
Lube #2 is disabled on OIL PUMP 2 Screen or com-
pressor #1 enters the prelube state.
“WARNING – LOW OIL LEVEL”
(Software version C.MLM.11.02.xxx (and later) or
C.OPT.11.02.300 (and later)).
Displayed if the oil level in the oil sump is < the Mini-
mum Oil Level as shown below. It will automatically
clear when the level is > Minimum Oil Level.
Condition Minimum Oil Level
No compressors running 50%
1 compressor running 40%
2 compressors running 30%
“WARNING – OIL PUMP #1 – SEAL LUBRICA-
TION IN PROGRESS”
The 2 minute seal lubrication cycle (that occurs once
every 24 hours while the compressor #1 is not run-
ning) is in progress for compressor #1.
“WARNING – OIL PUMP #2 – SEAL LUBRICA-
TION IN PROGRESS”
The 2 minute seal lubrication cycle (that occurs once
every 24 hours while compressor #2 is not running) is
in progress for compressor #2.
“WARNING – VANES #1 – UNCALIBRATED”
The Pre-rotation Vanes calibration procedure has not
been performed on compressor #1.
“WARNING – VANES #2 – UNCALIBRATED”
The Pre-rotation Vanes calibration procedure has not
been performed on compressor #2
“WARNING – SURGE PROTECTION - EXCESS
SURGE DETECTED”
(Applies only to single compressor operation and
only if the Surge Protection SHUTDOWN Setpoint
is disabled) The Surge Window Count has exceeded
the Count Limit setpoint during single compressor op-
eration. This message can be cleared with the Warning
Reset key in Operator access level (or higher) after the
Surge Window Count is < the Count Limit.
“WARNING – SURGE PROTECTION – EXCESS
SURGE LIMIT”
(Applies to single compressor operation only and only
if the Surge Protection EXTENDED RUN Setpoint is
enabled) The chiller is operating in a Surge Protec-
tion Extended Run period because the Surge Window
Count has exceeded the Count Limit setpoint during
single compressor operation. When the Surge Window
Count exceeds the Count Limit setpoint, a 10 minute
Extended Run period is initiated. During this period,
the Pre-rotation Vanes are driven closed. At the end
of the 10 minute period, if the Surge Window Count is
< the Count Limit, this message is cleared and Vanes
are allowed to load. Otherwise, another 10 minute Ex-
tended Run period is initiated.