SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.69-O1
ISSUE DATE: 9/30/2012
2
Zone Control Time Remaining
Displays the amount of time remaining in the 60-sec-
ond countdown timer when transitioning from Zone 2
to Zone 1. When transitioning from Zone 2 parameter
set to Zone 1 parameter set, the Zone 1 error require-
ment must be met for 60 continuous seconds before
Zone 1 parameters can be used.
Refrigerant Level Override Mode
Displays “Valve Preset” during pre-positioning of the
Refrigerant Level Control Valve while Starting the
lead compressor. Displays “Lag Start” while perform-
ing the Refrigerant Level Lag Start mode while starting
the Lag Compressor.
Override Time Remaining
If in refrigerant Level “Valve Preset” mode, displays
the time remaining in the Valve Preset Timer plus the
time remaining of the first 3 minutes of the Lead Com-
pressor Run Time. If in Refrigerant Level “Lag Start”
mode, displays the time remaining in the Lag Com-
pressor Pre- Lube cycle plus the time remaining in the
first 3.5 minutes of Lag Compressor Run Time.
Refrigerant Level Target
After the chiller has been running for 3 minutes, if
the refrigerant level is less than the Level Setpoint, a
linearly increasing ramp (Refrigerant Level target) is
applied to the Level Setpoint. This ramp allows the
level to go from the present level to the programmed
Level Setpoint over a period of time programmed as
the Ramp Up Time setpoint.
Ramp Up Time Remaining
Displays the time remaining in the Ramp Up time
countdown timer while a Refrigerant Level target ramp
is in effect.
Programmable
[Refrigerant Level Control] Raise (Manual)
This key puts the level control into manual mode and
sends a RAISE command to the variable orifice.
[Refrigerant Level Control] Lower (Manual)
This key puts the level control into manual mode and
sends a Lower command to the variable orifice.
[Refrigerant Level Control] Hold] (Manual)
This key puts the level control into manual mode and
sends a Hold command to the variable orifice.
[Refrigerant Level Control] Auto
This key puts the level control into automatic mode.
Setpoint
Specifies the desired refrigerant level to be maintained
in the condenser.
Valve Preset Time
Specifies the duration of the pre-positioning (close)
pulse during the lead compressor System Prelube.
Ramp Up Time
Specifies the duration of the ramp-up time applied to
the Refrigerant Level Target when starting the lead
compressor while the actual refrigerant level is less
than the level setpoint, after a 3 minute bypass at start.
Period (Zone 1)
Specifies the control period used during Zone 1 opera-
tion.
Rate (Zone 1)
Specifies the rate limit threshold used during Zone 1
operation.
Period (Zone 2)
Specifies the control period used in Zone 2 operation.
Rate (Zone 2)
Specifies the rate limit threshold used during Zone 2
operation.
Navigation
Home
Access Level Required
: SERVICE
Causes a return to the Home Screen
Condenser
Access Level Required:
SERVICE
Causes a return to the Condenser Screen