SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.69-O1
ISSUE DATE: 9/30/2012
2
Compressor Status
Displays whether compressor #1 has been selected as
the lead or Lag compressor. The lead compressor is se-
lected upon receipt of a start signal. The compressor
that has the least amount of run time that is ready to run
is selected as the lead compressor.
% Full Load Amps
Displays compressor #1 motor current as a percentage
of full load amps of the compressor #1 motor.
Pre-rotation Vanes Position
Displays the position (0% to 100%) of the pre-rotation
vanes.
Discharge Valve Close Command (LED)
Illuminates when a close command is being applied to
compressor #1 Discharge Valve.
Discharge Valve Open Command (LED)
Illuminates when an open command is being applied to
compressor #1 Discharge Valve.
Discharge Valve
Indicates the status of compressor #1 Discharge Valve
as closing, closed, opening or opened.
Programmable
Software version C.OPT.11.03.01.004 (and later) does
not allow manual Pre-rotation Vanes control on a shut-
down compressor while the other compressor is run-
ning. This helps minimize rotation of this compressor
if its Discharge Valve is not fully sealed.
Pre-rotation Vanes Open (Manual)
This key puts the vane control into manual mode and
applies an open command to the vanes.
Pre-rotation Vanes Close (Manual)
This key puts the vane control into manual mode and
applies a close command to the vanes.
Pre-rotation Vanes Hold (Manual)
This key puts the vanes into manual mode and applies
a hold command to the vanes.
Pre-rotation Vanes Auto
This key returns the vane control to automatic mode.
Discharge Valve (Manual/Auto)
Only displayed if compressor #1 is stopped. This key
puts compressor #1 Discharge Valve in manual or au-
tomatic operation. When in manual operation, this key
is used to manually open or close the valve.
Navigation
Home
Causes an instant return to the Home Screen.
Compressor
Causes an instant return to the Main Compressor
Screen.
Proximity Probe Calibrate
Only available if chiller is stopped. Moves to the sub-
screen that allows calibration of the High Speed Thrust
Bearing Proximity Probe for compressor #1.
Pre-rotation Vanes Calibrate
Only available if the chiller is stopped. Moves to the
sub-screen that allows calibration of the Pre-rotation
Vanes for compressor #1.
VGD
(Software version C.MLM.11.02.xxx (and later) or
C.OPT.11.02.300 (and later))
Access Level Required:
SERVICE
Only displayed if VGD feature enabled on Operations
Screen. Moves to the sub-screen that allows viewing
and programming of the Variable Geometry Diffuser
(VGD) feature for compressor #1. Service technicians
refer to Service manual 160.69-M1