JOHNSON CONTROLS
85
SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.69-O1
ISSUE DATE: 9/30/2012
2
Shutdown
(Software version C.OPT.11.03.01.004 and later)
Access Level Required:
SERVICE
If the Auto Lube setpoint above is set to DISABLED,
the SHUTDOWN Setpoint is used to enable or dis-
able the safety shutdown that occurs at 1400 operating
hours since last lubrication. The safety shutdown can
be enabled or disabled per the customer’s preference. If
enabled, the safety shutdown will occur at the normal
1400 hours. If disabled, a warning will be displayed
but the safety shutdown will not occur. Service Techni-
cians refer to procedure in Service Manual 160.69-M1.
Navigation
Home
Access Level Required:
VIEW
Causes an instant return to the Home Screen.
Motor
Access Level Required:
VIEW
Causes an instant return to the Motor Screen.