SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.69-O1
ISSUE DATE: 9/30/2012
2
SETUP SCREEN
Overview
This screen is the top level of the general configura-
tion parameters. It allows programming of the time and
date, along with specifications as to how the time will
be displayed (12 or 24 hour format). In addition, the
chiller configuration, as determined by the state of the
Microboard Program Jumpers and Program Switches
is displayed. A qualified Service Technician, follow-
ing instructions in YORK Service Manual 160.69-M1,
establishes this configuration per the desired opera-
tion. This screen also serves as a gateway to more sub-
screens for defining general system parameters.
Display Only
031-01730-000 Microboard
Chilled Liquid Pump Operation:
Displays
Standard
or
Enhanced
Refrigerant Selection:
Displays
R134a
Anti-Recycle:
Displays
Disabled
or
Enabled
Power Failure Restart:
Displays
Manual
or
Automatic
Liquid Type:
Displays
Water
or
Brine
Coastdown:
Displays
Standard
(150 seconds) or
Enhanced
(15
minutes – Steam Turbine applications)
Pre-Run:
Displays
Standard
(50 seconds) or
Extended
(180
seconds)
031-02430-000 & 031-02430-001 Microboard
Refrigerant Selection
Displays R22 or R134a
Liquid Type
Displays Water or Brine
Programmable
Set Date
Access Level Required:
OPERATOR
Allows the user to specify the present date. This value
is critical to logging system shutdowns accurately and
for utilizing the scheduling capabilities. When prompt-
ed to enter a date value, the user must enter the day,
month, and four-digit year (using leading zeroes as
necessary). If within range, the value will be accepted.
If out of range, the user is prompted for the information
again. At this point the user may retry the date entry, or
cancel the programming attempt.
50058
FIGURE 30 -
SETUP SCREEN
LEAVING CHILLED LIQUID CONTROL