JOHNSON CONTROLS
140
FORM 160.69-O1
ISSUE DATE: 9/30/2012
SECTION 3 – PRINTERS
YORK UPDATE
CHILLER ID 0
(c) 1997 – 2001 YORK INTERNATIONAL CORPORATION
Mon 22 Nov 1999 8:50:45 AM
SYSTEM RUN
LEAVING CHILLED LIQUID CONTROL
[List all warnings presently active]
Controls C.MLM.01.06.102
Run Time 0 Days 2 Hr 59 Min
Operating Hours
= 25 Hr
Number Of Starts
= 6
Control Source
= Local
Evaporator
-----------------------------------------------------------------------------------
Leaving Chilled Active Setpoint
= 45.0 ~F
Chilled Liquid Pump
= Run
Chilled Liquid Flow Switch
= Closed
Leaving Chilled Liquid Temperature
= 45.0 ~F
Return Chilled Liquid Temperature
= 55.0 ~F
Evaporator Pressure
= 75.0 Psig
Evaporator Saturation Temperature
= 44.4 ~F
Evaporator Refrigerant Temperature
= 44.5 ~F
[If Refrigerant Sensor enabled]
Small Temperature Difference
= 0.5 ~F
Condenser
-----------------------------------------------------------------------------------
Condenser Liquid Pump
= Run
Condenser Liquid Flow Switch
= Closed
Leaving Condenser Liquid Temperature
= 95.0 ~F
Return Condenser Liquid Temperature
= 85.0 ~F
Condenser Pressure
= 200.0 Psig
Condenser Saturation Temperature
= 101.4 ~F
Small Temperature Difference
= 6.4 ~F
Drop Leg Refrigerant Temperature
= 83.0 ~F
[If Drop Leg Sensor enabled]
Sub Cooling Temperature
= 18.4 ~F
[If Drop Leg Sensor enabled]
Compressor
-----------------------------------------------------------------------------------
Discharge Temperature
= 120.0 ~F
Liquid Line Solenoid
= On
[If Mod C Chiller]
Vent Line Solenoid
= On
[If Mod D Chiller or higher]
Oil Sump
-----------------------------------------------------------------------------------
Oil Pump Run Output
= On
Sump Oil Pressure (LOP)
= 75.8 Psig
Pump Oil Pressure (HOP)
= 124.6 Psig
Oil Pressure
= 47.8 Psid
Oil Sump Temperature
= 150.0 ~F
Oil Heater
= Off
[If Mod D Chiller or higher]
Oil Return Solenoid
= Off
[If Mod D Chiller or higher]
FIGURE 49 -
SAMPLE PRINTOUT (STATUS)
[Skip the following section if Hot Gas Bypass is not
enabled]
Hot Gas
-----------------------------------------------------------------------------------
Valve Position
= 15 %
Pre-Rotation Vanes Position
= 75 %
Surge
-----------------------------------------------------------------------------------
Total Surge Count
= 127
Surge Window Time
= 1 Min
Surge Window Count
= 0
[Skip the following section if Variable Speed Oil
Pump is not installed]
Variable Speed Oil Pump
-----------------------------------------------------------------------------------
Oil Pump Drive Command Frequency
= 25.0 Hz
Pulldown Time Remaining
= 9.0 Min
[If Pulldown in effect]
[Skip the following section if Liquid Level is not
enabled]
Refrigerant Level Control
-----------------------------------------------------------------------------------
Refrigerant Level Position
= 35 %
Ramp Up Time Remaining
= 15 Sec
[If Ramp Up in effect]
Proximity Probe
-----------------------------------------------------------------------------------
High Speed Thrust Bearing Proximity Differen = 2 Mils
High Speed Thrust Solenoid
= On
[If Mod C Chiller]
[Skip the following section if Motor Type is not EM]
Electro-Mechanical Starter
-----------------------------------------------------------------------------------
Motor Run
= On
% Full Load Amps
= 94 %
[Skip the following section if Motor Type is not Mod A SSS]
Liquid-Cooled Solid State Starter
-----------------------------------------------------------------------------------
Motor Run
= On
% Full Load Amps
= 94 %
Phase A Voltage
= 447 V
Phase B Voltage
= 409 V
Phase C Voltage
= 442 V
Phase A Current
= 193 A
Phase B Current
= 204 A
Phase C Current
= 190 A
[Skip the following section if Motor Type is not Mod
B SSS]
Liquid-Cooled Solid State Starter
-----------------------------------------------------------------------------------
Starter Model
= 26L
Motor Run
= On
% Full Load Amps
= 95 %
kW Hours
= 20723 kWH
Input Power
= 8225 kW
FIGURE 49 -
SAMPLE PRINTOUT (STATUS) (CONT'D)