JOHNSON CONTROLS
35
SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.69-O1
ISSUE DATE: 9/30/2012
2
EVAPORATOR SCREEN
Overview
This screen displays a cutaway view of the chiller
evaporator. All setpoints relating to the evaporator side
of the chiller are maintained on this screen. Animation
of the evaporation process indicates whether the chiller
is presently in a
RUN
condition. Animation of the liq-
uid flow indicates chilled liquid flow.
Display Only
Chilled Liquid Flow Switch (Open / Closed)
Displays whether the liquid flow is present in the evap-
orator.
Chilled Liquid Pump
Displays the command presently sent by the control
center to the Chilled Liquid Pump (RUN or STOP).
Evaporator Pressure
Displays the present refrigerant pressure in the evapo-
rator.
Evaporator Saturation Temperature
Displays the present saturation temperature in the
evaporator.
Return Chilled Liquid Temperature
Displays the temperature of the liquid as it enters the
evaporator.
Leaving Chilled Liquid Temperature
Displays the temperature of the liquid as it leaves the
evaporator.
Evaporator Refrigerant Temperature
Displays the temperature of the refrigerant in the evap-
orator, if the sensor is present.
Small Temperature Difference
Displays the difference between the Leaving Chilled
Liquid temperature and the Evaporator Refrigerant
temperature. The Evaporator Refrigerant temperature
will be represented by the Refrigerant Temperature
sensor input if the sensor is present, otherwise it will be
represented by the Evaporator Saturation temperature.
Leaving Chilled Liquid Temperature Setpoints –
Setpoint
Displays the present setpoint to which the chiller is op-
erating, whether controlled locally or remotely.
Leaving Chilled Liquid Temperature Setpoints -
Shutdown
Displays the Leaving Chilled Liquid Temperature at
which the chiller will shut down to avoid over-cooling
the building. By default this value is 4°F below the
Leaving Chilled Setpoint.
00301VIPC
FIGURE 6 -
EVAPORATOR SCREEN