APPENDIX 1 - CHECKLIST
FORM 155.32-ICOM2.EN.UL
ISSUE DATE:1/10/2018
178
JOHNSON CONTROLS
JOHNSON CONTROLS
6
FORM 155.32-CL1
ISSUE DATE: 03/31/2017
COMBUSTION DATA
MEASURED BY
SPECIFI-
CATION
STAN-
DARD
LOW
MIDDLE
HIGH
OUTPUT VALUE
%
Control panel
FUEL DAMPER POSITION
%
Damper pointer
AIR DAMPER POSITION
%
Damper pointer
FUEL PRIMARY PRESSURE
(P1)
Pressure gauge
FUEL SECONDARY PRES-
SURE (P2)
Pressure gauge
FUEL CONSUMPTION (SEE
NOTES)
ft
3
/h
Flow meter
FUEL CONSUMPTION (SEE
NOTES)
ft
3
N/h
&DOFXODWLRQRUÀRZ
meter
EXHAUST GAS O
2
CON-
CENTRATION
%
Exhaust gas analyzer
4.0~8.0
EXHAUST GAS CO CON-
CENTRATION
ppm
Exhaust gas analyzer
EXHAUST GAS CO
2
CON-
CENTRATION
%
Exhaust gas analyzer
WIND BOX PRESSURE
Water manometer
DRAFT PRESSURE (P3)
Water manometer
0~
,1:&
FURNACE PRESSURE (P4)
Water manometer
FLAME CURRENT
ȝ$
Flame current meter
BURNER FAN OPERATION
CURRENT
A
Cramp meter
EXHAUST GAS TEMPERA-
TURE
°F
Control panel
DIRECT FIRED ABSORPTION CHILLER-HEATER COMMISSIONING DATA SHEET (2/3)
NOTES:
,IJDVIORZUDWHLVWDNHQDV
IW
3
/h, calculate
IW
3
N/h with fuel pressure and ambient temperature.
LD20247
P1
P2
Air
P3
P4
Gas
Ambient temperature:
°
)