SECTION 5 - COMMISSIONING
FORM 155.32-ICOM2.EN.UL
ISSUE DATE:1/10/2018
86
JOHNSON CONTROLS
STOP THE CHILLER-HEATER
1. Press the
STOP
button on the Main screen of the Control Panel. To stop the chiller-
heater from a remote location, enter the remote stop signal.
When the chiller-heater stops, the following occurs:
• The capacity control valves close.
• Combustion stops.
• The dilution operation starts, and continues for 7 - 30 minutes.
• During the dilution operation, the solution circulation pump, the solution spray pump,
and the refrigerant pump are in operation.
• Once the dilution operation is complete, the solution circulation pump, the solution
spray pump, and the refrigerant pump stop. Then, the chilled/hot water pump, the
cooling water pump, and the cooling tower fan stop.
INTERLOCKING PROCEDURE
Operating the chiller-heater in cooling mode without the air conditioner running can cause
the chilled water to freeze. If the unit contains only one air conditioner, secure the air
conditioner interlock.