SECTION 5 - COMMISSIONING
ISSUE DATE:1/10/2018
JOHNSON CONTROLS
87
Figure 41 -
Cooling Start/Stop Diagram
LD22952
Remote / local operation
change
Power on
Initialize self-check
mechanism
Chilled/Cooling/Hot Water
pump start
Chilled/Cooling/ Hot
water pump interlock
ON?
Solution pump and
refrigerant pump start
Hold low combustion
Local start operation
Remote start operation
Air conditioning machine
and cooling tower fan run
Abnormal warning
Remote
Local
No
3 minutes
Time up
Temperature control
operation
Yes
Burner fan starts
Yes
Stop Operation
Dilution operation starts
Combusiton Stops
Dilution time increasing
Chilled Water/ or
refrigerant temp.
low cut-out
Dilution
time stops
increasing
Yes
Solution Pump/
Refrigerant Pump
stop running
Dilution time up
Solution Pump/
Refrigerant Pump
continue running
HT-GEN1
pressure low
No
1
Pass 30 minutes
after dilution starts
No
No
Yes
Yes
Solution Pump/
Refrigerant Pump
stop
Chilled/Hot/
Ccoling water
pump stop
Absorption chiller
stops
Air Conditioning
Machine/Cooling
Tower Fan stop
Burner Stops
1
No