SECTION 5 - COMMISSIONING
FORM 155.32-ICOM2.EN.UL
ISSUE DATE:1/10/2018
88
JOHNSON CONTROLS
Figure 42 -
Direct Fire Sequential Flowchart
NOTES:
1. Be sure to implement sequential operation of the chilled water pump, the cooling water pump, and the hot water pump from the chiller.
2. If there is only one air conditioner, secure interlock for the air conditioner operation (the part indicated by broken lines shown in the diagram above).
3. Implement sequential operation in such a way that when the chilled water pump stops, the cooling water pump, and the hot water pump also stop.
4. If the hot, chilled and cooling water system is the common system, you must install the isolation valve on the hot water, chilled water and cooling water inlet pipe entering the chiller, and
interlock these isolation valves with the chiller control panel. It is important for safe and reliable operation of the chiller as well as to prevent potential crystallization of LiBr solution and
freezing of the evaporator tubes.
Figure 43 -
Stopping absorption chiller-Heater Direct Fire Flowchart
NOTES:
1. Verify that the air conditioner has stopped after the chiller dilution operation is complete. Otherwise, the chiller may become damaged due to freezing of the chilled water and/or
crystallization of the solution.
2. The installation and interlocking of these valves with the chiller control panel is mandatory for safe and reliable operation of the chiller and to prevent potential crystallization of LiBr solution
and freezing of the evaporator tubes.
LD22953
Chiller - Heater
Chilled/Hot Water
Pump
Sequential
Operation
AND
Air Conditioner
Cooling Water Pump
Cooling Tower
AND
Interlock
Sequential
Operation
(2)
(3)
Sequential
Operation
Interlock
Other interlocks, including earthquake sensor, abnormal room temperature sensor, and so on.
Sequential
Operation
LD22954
Not completed
AND
Chiller - Heater
dilution operation
begins
Chiller-Heater dilution
operation completed
Stop the chiller-heater
Completed
Chilled/hot water pump
and air conditioner stop
Stop the air
conditioner