SECTION 6 – OPERATION
ISSUE DATE:1/10/2018
JOHNSON CONTROLS
103
The Cooling Water section shows you:
Inlet Temperature:
temperature of the cooling water measured as it enters the absorber
Outlet Temp.:
temperature of the cooling water measured as it leaves the condenser
Refrigerant Temp.:
temperature of the refrigerant in the evaporator.
Absorber Temp.:
temperature of the diluted solution in the absorber
Exhaust G Temp.:
temperature of the exhaust gas measured as it leaves the high
temperature generator
HG Temperature:
temperature of the concentrated solution in the high temperature
generator
HG Pressure:
pressure in the high temperature generator
HG Concentration:
concentration of the concentrated solution in the high temperature
generator
Control Valve:
percentage that the valve is open
To move to another history screen, press the desired screen button to move to the desired
screen in the history menu: Hourly Operation, Failure, or Alarm.
There are two sets of buttons on the right side of the screen. The first set gives you access
to information about past occurrences. For instance, if you press the
3 times ago
button,
you will see the settings as they appeared 3 minutes ago.
The buttons in the History Menu section allow you to move between the various screens:
Hourly Operation:
Press this button to access the Hourly Operation History screen
Minutely Operation:
Press to view the Minutely Operation History screen
Failure History:
Press this button to see the Failure History screen
Alarm History:
Press to see the Alarm History screen.
To move to another screen, press the any of the available buttons along the bottom of the
screen.