SECTION 6 – OPERATION
FORM 155.32-ICOM2.EN.UL
ISSUE DATE:1/10/2018
119
JOHNSON CONTROLS
Figure 57 -
Changeover Valve Locations for Chiller with Evaporator Heating
Table 33 -
Changeover Valve Operation for Chiller with Evaporator Heating
OPERATION
MODE
VALVE OPERATION/LOCATION
HG ->E
Ref
E->A
Ref
LG ->C Ref
Return
HG Sol
Supply
HG Sol
Return
RHW Ref
Supply
RHW Ref
Return
LG->HG
Ref Return
Purge valves
Cooling
X
X
Ø
Ø
Ø
X
X
X
Set to automatic
purge of the purging
tank
Heating
Ø
Ø
Ø
Ø
Ø
X
X
X
Close V10, V11,
V12. V13. V14,
V15, V16
Simultaneous
cooling and
residential hot
water supply
X
X
Ø
Ø
Ø
Ø
Ø
X
Set to automatic
purge of the purging
tank
Simultaneous
heating and
residential hot
water supply
Ø
Ø
Ø
Ø
Ø
Ø
Ø
X
Close V10, V11,
V12. V13. V14,
V15, V16
Residential hot
water supply
(sole mode)
X
X
X
X
X
Ø
Ø
Ø
Close V10, V11,
V12. V13. V14,
V15, V16
V11
V1
V4
P11
63
SH1
VH
M
63G P13
V8
VK
SV3
VJ
V3
LG4
Condenser
Low Temp.
Generator
LD19987a
V24
UL Only
Evaporator
(Upper)
Absorber
(Upper)
Absorber
(Lower)
Evaporator
(Lower)
Purge Pump
Oil Trap
Check
Valve
Pressure
Release
Valve
Gas Inlet
High Temp.
Heat
Exchanger
High Temp.
Generator
Pilot Piping
Main Piping
BURNER
Control
Motor
Low Temp.
Heat
Exchanger
Refrigerant Pump
Solution
Circulation Pump
Solution
Spray Pump
Low Temp.
Generator Drain
Heat Exchanger
Chilled Water
Cooling Water
Refrigerant
Diluted Solution
High Concentrated Solution
Cooling
Water
Outlet
Cooling
Water
Inlet
Residential Hot Water
Chilled
Water
Outlet
Chilled
Water
Inlet
Purge
Tank
Gas Separator
Exhaust
Gas Outlet
AP
M
SV1SV2
PI2
69
WC1
V14
V16
V13
V11
V10
P/T1
V21
V20
V12
V15
V1
M
T
RHW
Outlet
RHW
Inlet
RTD1
RTD2
QRA
TH4
T/C3
TH1
P/T1
T/C1
T/C2
RTD3
T/C5
T/C4
44.6°F
53.6°F
140°F
113°F