FORM 155.32-ICOM2.EN.UL
SECTION 7 – MAINTENANCE
ISSUE DATE:1/10/2018
JOHNSON CONTROLS
133
Figure 66 -
YHAU-CGN/H Direct Fired Chiller-Heater with Evaporator Heating Flow Diagram -
Simultaneous Heating and Residential Hot Water
Table 36 -
Purge Valve Operation
O: Fully open valve. X: Fully closed valve.
PURGING
PATTERN
USE
OPERATION
VALVE OPERATION/LOCATION
V10
V11
V14
V13
V16
A
Check capacity of vacuum pump
–
x
O
x
x
B
Direct purging from absorber
Preparation
x
O
O
x
Starting
purging
x
O
O
O
C
Manual purging from purging tank
Preparation
O
x
O
x
x
Starting
purging
O
O
O
x
x
D
Automatic purge of the purging tank
O
O
O
x
x
V11
V1
V4
P11
63
SH1
VH
M
63G P13
V2
VK
SV5
VJ
V3
Condenser
Low Temp.
Generator
LD19989a
V24
Evaporator
(Upper)
Absorber
(Upper)
Absorber
(Lower)
Evaporator
(Lower)
140°F
131°F
194°F
113°F
Gas Inlet
High Temp.
Heat
Exchanger
High Temp.
Generator
Burner
Control
Motor
Low Temp.
Heat
Exchanger
Solution
Circulation Pump
Solution
Spray Pump
Low Temp.
Generator
Drain
Heat Exchanger
Hot Water
Refrigerant
Diluted Solution
High Concentrated Solution
Cooling
Water
Outlet
Cooling
Water
Inlet
Hot
Water
Outlet
Hot
Water
Inlet
Residential Hot Water
Gas Separator
Pressure
Release
Valve
Purge Pump
Oil Trap
Check
Valve
Purge
Tank
Exhaust
Gas Outlet
AP
M
SV1SV2
PI2
69
WC1
V14
V16
V13
V11
V10
V1
P/T1
V21
V20
V12
V15
M
T
RHW
Outlet
RHW
Inlet
RTD1
RTD2
QRA
TH4
T/C3
TH1
P/T1
T/C1
T/C2
RTD3
T/C5
T/C4