APPENDIX 1 - CHECKLIST
FORM 155.32-ICOM2.EN.UL
ISSUE DATE:1/10/2018
180
JOHNSON CONTROLS
JOHNSON CONTROLS
8
FORM 155.32-CL1
ISSUE DATE: 03/31/2017
TABLE 1 -
PURGE AMOUNT MEASUREMENT DATA SHEET (1/1)
User:
Model: YHAU -
MFG.No.:
User's machine code:
Measured Date:
Measured by:
Purge Amount from Purge Line
Flame Reaction Test
Standard: 4.0 cc/min. or smaller
Reaction (Strong/Weak/None)
Amount of Gas (P) cc/min
Purge Amount from Purge Tank
Elapsed time
1 hour
Consumed time for measurement (m)
min.
Total gas amount (a)
cc
Actual gas amount (b)
cc
(b) = (a) - (P) x (m)
Purge Amount from Absorber
Standard: 4.0 cc/min. or smaller
Elapsed time (T)
min.
1
2
3
5
10
15
20
30
Total gas amount (A)
cc
Increased gas amount (B)
cc
Actual gas amount (C)
cc/min.
(B) = (A) - previous(A)
(B) - (P) x { (T) - previous(T) }
(C) = (T) - previous(T)