FORM 155.32-ICOM2.EN.UL
SECTION 4 - TECHNICAL DATA
ISSUE DATE:1/10/2018
JOHNSON CONTROLS
44
Table 10 -
Electrical Data - CG/AN
YHAU-CG/AN
POWER SOURCE
(V-PH-HZ)
CIRCUIT BREAKER
SOLUTION
CIRCULATION PUMP
SOLUTION
SPRAY PUMP
RATED CURRENT
FRAME SIZE
KW
FLA
LRA
KW
FLA
LRA
150 EX(H/S)
AC460V-3Ph-60Hz
20 A
125 A
2.2
5.2
24.0
1.1
3.0
12.9
180 EX(H/S)
AC460V-3Ph-60Hz
25 A
125 A
2.2
5.2
24.0
2.2
5.2
24.0
240 EX(H/S)
AC460V-3Ph-60Hz
25 A
125 A
2.2
5.2
24.0
2.2
5.2
24.0
300 EX(H/S)
AC460V-3Ph-60Hz
30 A
125 A
3.0
7.1
31.0
2.2
5.2
24.0
360 EX(H/S)
AC460V-3Ph-60Hz
35 A
125 A
3.0
7.1
31.0
2.2
5.2
24.0
400 EX(H/S)
AC460V-3Ph-60Hz
35 A
125 A
3.0
7.1
31.0
2.2
5.2
24.0
450 EX(H/S)
AC460V-3Ph-60Hz
40 A
125 A
5.5
11.1
68.0
2.2
5.2
24.0
500 EX(H/S)
AC460V-3Ph-60Hz
40 A
125 A
5.5
11.1
68.0
2.2
5.2
24.0
560 EX(H/S)
AC460V-3Ph-60Hz
40 A
125 A
5.5
11.1
68.0
2.2
5.2
24.0
600 EX(H/S)
AC460V-3Ph-60Hz
45 A
125 A
5.5
11.1
68.0
2.2
5.2
24.0
700 EX(H/S)
AC460V-3Ph-60Hz
45 A
125 A
5.5
11.1
68.0
2.2
5.2
24.0
800 EX(H/S)
AC460V-3Ph-60Hz
35 A
125 A
5.5
11.1
68.0
2.2
5.2
24.0
900 EX(H/S)
AC460V-3Ph-60Hz
35 A
125 A
5.5
11.1
68.0
2.2
5.4
24.5
1000 EXW(H/S)
AC460V-3Ph-60Hz
50 A
125 A
7.5
16.5
76.0
2.2
8.8
38.0
1100 EXW(H/S)
AC460V-3Ph-60Hz
60 A
125 A
7.5
16.5
76.0
3.7
8.8
38.0
1200 EXW3(H/S)
AC460V-3Ph-60Hz
60 A
125 A
7.5
16.5
76.0
3.7
8.8
38.0
1300 EXW3(H/S)
AC460V-3Ph-60Hz
70 A
125 A
7.5
16.5
76.0
3.7
8.8
38.0
1400 EXW3(H/S)
AC460V-3Ph-60Hz
70 A
125 A
7.5
16.5
76.0
3.7
8.8
38.0
1500 EXW3(H/S)
AC460V-3Ph-60Hz
70 A
125 A
7.5
16.5
76.0
3.7
8.8
38.0
1600 EXW3(H/S)
AC460V-3Ph-60Hz
70 A
125 A
7.5
16.5
76.0
3.7
8.8
38.0