The following table contains information about the communication specifications required by the Modbus/RTU.
Communication protocol
Modbus/RTU
Communication path type
RS422/RS485 Data Length: 8 Bit Stop Bit: 1 Bit Parity: EVEN Speed:
9600 bps
Connector
D-Sub 9pin
Function Code
Read Coil Status: 01 Read Holding Register: 03
Device
Digital Signal: Coil Analog Signal: Holding Register
Slave Equipment Address
1
TABLE 22 -
COMMUNICATION SPECIFICATION - MODBUS/RTU