JOHNSON CONTROLS
99
SECTION 5 - COMMISSIONING
FORM 155.30-ICOM2.EN.UL
ISSUE DATE: 12/21/2018
5
JOHNSON CONTROLS
6
FORM 155.30-CL1.EN.UL
ISSUE DATE:12/11/2018
TABLE 1 -
COMMISSIONING DATA SHEET (1/2) (HOT WATER SINGLE-EFFECT ABSORPTION CHILLER)
User:
Model:
MFG.No.:
User's machine code:
Insulation Resistance
Electric Power Supply
Standard: 5 MΩ or more (with 500 V meg
-
ger)
R-Gnd
S-Gnd
T-Gnd
Specification: AC
V /
Hz
Circuit breaker
MΩ
Standard: /- 10% of spec.
R-S
V
U-Gnd
V-Gnd
W-Gnd
R-T
V
Solution circulation pump
MΩ
S-T
V
Solution spray pump
MΩ
R-Gnd
V
Refrigerant pump
MΩ
S-Gnd
V
Purge pump
MΩ
T-Gnd
V
Thermal Relay Setting
Refrigerant Purity
Temperature Setting
Solution circulation pump
A
Standard: 1.040 (kg/L) or less
Cooling
Solution spray pump
A
Specific gravity
Set. base temp.
°F
Refrigerant pump
A
Turbidity
Auto. stop temp.
°F
Purge pump
A
Auto. restart diff.
°F
Pump Discharge Pressure
Purge Amount
Solution circulation pump
PSIG Standard: 4 cc/min or less
Solution spray pump
PSIG Purge tank
cc
Refrigerant pump
PSIG Absorber
cc