Mod “A” Solid State Starter screen
Figure 35: Mod “A” Solid State Starter screen
This screen displays all information pertaining to the Mod “A” Solid State Starter.
Table 94: Display only
Field/LED name
Description
Motor Run (LED)
Indicates whether the digital output from the controls is
commanding the motor to RUN.
Motor Heater (LED)
Indicates whether the optional Motor Heater is ON or OFF.
Motor Current % Full Load
Amps
Displays the motor current as a percentage of the Full Load Amps
(FLA) value. This is the data returned by the Starter Logic Board for
the Solid State Starter.
Current Limit Setpoint
Displays the current limit value in use. This value could come from
a 0 to 20mA, 4 to 20mA, 0 to 10VDC or 2 to 10VDC input in Analog
Remote mode, PWM signal in Digital Remote mode, E-Link Gateway
interface in ISN mode, or a locally programmed value.
Pulldown Demand Time Left Displays the time remaining in the programmed pulldown period if
the value is nonzero.
Scale/Model
Display information about the Liquid Cooled Solid State Starter
Rating and the maximum allowed Full Load Amps.
Voltage – Phase A, B, C
Display the 3-phase input line voltage values being read from the
Solid State Starter.
Current – Phase A, B, C
Display the 3-phase motor current values being read from the Solid
State Starter.
YK-EP Style B Centrifugal Chiller
100
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...