Table 106: Display only
Field/LED name
Description
Input Power
Displays the total kilowatts measured by the MVVSD. Value is
provided by the MVVSD.
KW Hours
Displays the cumulative amount of kilowatts used over time as the
VSD motor operates. Value is calculated by the OptiView Control
Center from the Input Power value provided from the MVVSD.
Pre-Rotation Vanes Position Displays the Pre-Rotation Vane position as a value between 0 and
100%.
VSD Cooling Fans Output
(LED)
Illuminates when the VSD cooling fans are being commanded to
run.
Precharge Relay Output
(LED)
Illuminates when the pre-charge relay is commanded to energize.
Output Current (Phase A, B,
C)
Displays the three phases of output current to the motor.
DC Bus Voltage (Phase A, B,
C)
Displays the three phases of DC Bus voltage
MVVSD Model
Displays the model number as received from the MVVSD. The model
number is displayed as a number representing the horsepower
rating (ie; 1500HP). It is derived from the Motor Rated Voltage
and the Programmed Drive Current values received from the MV-
VSD according to the following table Table 107. If this results in a
model that is not defined in the lookup table, the model number is
displayed as INVALID and the chiller will not be allowed to run while
this is displayed.
Motor Voltage Rating
Displays the voltage rating of the MVVSD as received from the
MVVSD. This is the Motor Voltage Rating as received from the
MVVSD. Displayed as 1300V, 3300V or 4160V. If an invalid value is
received, "Invalid" is displayed and the chiller will not be allowed to
run.
Output Frequency Rating
This is the rated output frequency as received from the MVVSD.
This value is the maximum drive frequency (Hz) when the MVVSD
receives a 100% speed command from the OptiView Control Center.
If the value received is not 50 Hz or 60 Hz, INVALID is displayed. If
this is the case, then the Motor Voltage Rating (above) determines
the maximum frequency as follows:
Motor voltage rating
Output frequency rating
2300 or 4160 V
60 Hz
3300 V
50 Hz
Table 107: Motor rated voltage (V)*
Model in HP
2300 V
3300 V
4160 V
500
107 A
78 A
62 A
600
129 A
93 A
74 A
700
157 A
110 A
87 A
800
172 A
124 A
99 A
109
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...