Table 130: Display only
Field/LED name
Description
Pre-Rotation Vanes Position
If equipped with a Pro-rotation Vanes potentiometer, displays the
present Pre-Rotation Vanes position as a value between 0% (closed)
and 100% (full open).
Motor Windings
Temperature
Displays the enabled Motor Winding Temperatures for phase A, B
and C. The setting of the Winding Temperature Protection Setpoint
affects this display as follows: When winding RTD's are enabled,
there are 2 temperatures per phase displayed (otherwise, there
is only 1 per phase). When set to Disabled, no temperatures are
displayed and the heading, text and data boxes do not appear.
Individual temperatures can be disabled using the Temperature
Disable Setpoint (on the MOTOR SETPOINTS Screen). When an
individual temperature is disabled, the temperature data box
does not appear. Any RTD input that registers as an open RTD is
considered invalid and displays as XXX.X.
Average Winding
Temperature
This value is calculated as the average of all enabled and valid Motor
Winding Temperatures. Any winding temperature that registers as
open, out of range or disabled is not used in the calculation. When
RTD's are used for winding temperature measurement, there are a
maximum of 6 temperatures used to calculate the average. When
transmitters are used, there are a maximum of 3 temperatures used
to calculate the average. The text description and data box do not
appear when the Winding Temperature Protection Setpoint is set to
disabled.
Motor Cooling Coil Leak
Detected (LED)
Illuminates when the enabled Motor Cooling Coil Leak Detector
(refer to
Motor Cooling Coil Leak Protection
leak. The LED and text description do not appear when the Motor
Cooling Coil Leak Protection Setpoint is set to Disabled.
Motor Bearings
Temperature
Displays the enabled Shaft End and Opposite End motor bearing
temperatures. Any RTD input that registers as an open RTD,
is considered invalid and displays as XXX.X. When the Bearing
Temperature Protection Setpoint is set to Disable, no temperatures
are displayed and the heading, text and data boxes do not appear.
131
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...