Table 135: Programmable
Button
Access level Description
The Vibration Baseline values from which the Vibration Shutdown
and Warning thresholds are derived, are displayed on the MOTOR
DETAILS Screen. The thresholds are calculated from the Baseline
values as follows: (NOTE: if the calculated value exceeds the
minimum and maximum limits of the Shutdown (2.0 to 30.0) or
Warning (1.0 to 15.0) threshold, the threshold is set to the respective
upper or lower limit).
•
Shaft End High Vibration Warning - Shaft End Vibration
Baseline X2
•
Shaft End High Vibration Warning Default - Shaft End
Vibration Baseline X2
•
Opposite Shaft End High Vibration Warning - Opposite End
Vibration Baseline X2
•
Opposite Shaft End High Vibration Warning Default - Opposite
End Vibration Baseline X2
•
Shaft End High Vibration Shutdown - Shaft End Vibration
Baseline X3
•
Shaft End High Vibration Shutdown Default - Shaft End
Vibration Baseline X3
•
Opposite Shaft End High Vibration Shutdown - Opposite Shaft
End Vibration Baseline X3
•
Opposite Shaft End High Vibration Shutdown Default -
Opposite Shaft End Vibration Baseline X3
If no baseline values are entered, by either the auto baseline routine
or manual entry, the message WARNING – MOTOR – BEARING
VIBRATION BASELINE NOT SET is displayed and the baseline values
are set to X.X while this message is displayed. When the Motor
Vibration Protection Setpoint is set to Disabled, no baseline vibration
values are displayed and the heading, text and data boxes do not
appear.
Table 136: Navigation
Button
Access level Description
Home
Service
Returns user to HOME screen.
Motor details Service
Returns user to Motor Details screen.
139
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...