Schedule screen
Figure 52: Schedule screen
The SCHEDULE Screen contains more programmable values than a normal display screen. As such,
each programmable value is not linked to a specific button. Instead the SELECT key is used to
enable the cursor arrows which are used to highlight the day and the start or stop time the user
wishes to modify. At this point the user may press the Enter key to program the Start/Stop times for
that day.
In order for the Start/Stop combination to be utilized, each Start time must have a corresponding
Stop time which occurs later in the day. The presently programmed schedule for a given day can
be cancelled by setting both the Start time and Stop time to 12:00 AM. If the Start time equals the
Stop time (with any time other than 12:00 AM), the chiller is OFF for that day. If the user desires the
chiller to operate continuously through several days, the Stop time of Day 1 can be set to 11:59 PM
and the Start time of Day 2 can be set to 12:00 AM. The chiller will not stop but continue to operate
until the stop of Day 2.
The user has the ability to define a standard set of Start/Stop times which are utilized every week.
The user may then specify exception Start/Stop combinations for any day of the week up to 6 weeks
in advance. At the end of each week the schedule for the next week is created by combining the
standard week definition and the next defined exception week. The schedule is then updated as
each of the exception weeks shifts down, leaving a new, blank exception week in the 6th week slot.
Table 147: Display only
Field/LED
name
Access level Description
None
–
153
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...