Trend setup screen
Figure 66: Trend setup screen
This screen is used to configure the TRENDING Screen. The parameters to be trended are selected
from the COMMON SLOTS Screen or Common Slots Master list and entered as Slot Numbers for
Data Points 1 through 6. The Y-Axis minimum and maximum values for each parameter are entered
as Data Point Min and Data Point Max for Data Points 1 through 6. The interval at which all the
parameters are sampled is selected as the Data Collection Interval.
Table 187: Programmable
Button
Access level Description
Chart Type
Operator
Selects Continuous, One Screen Or Triggered type of graph.
Select
Operator
This key is used to enter the Slot Numbers and the minimum and
maximum Y-Axis values of each parameter to be trended. Pressing
this key places a yellow box around Data Point 1 Slot Number. Use
the ▲ and ▼ navigation keys to place the box around the value
of Data Points 1 through 6 to be changed. With the desired value
selected, press the
X
key. A dialog box is displayed permitting data
entry.
Data Point
Slot #(1-6)
Operator
Use the SELECT key as described above and enter the Slot Number
from the COMMON SLOTS Screen or Master Slot Number List of
the desired parameter to be trended. The selected parameter
description will be displayed for the Data Point. Setting this Slot
Number to zero will disable trending for that particular Data Point.
Any or all points can be disabled.
YK-EP Style B Centrifugal Chiller
178
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...