Evaporator Refrigerant Temperature (RT7) has been enabled by a Service Technician using
instructions in
OptiView Control Center – Service Instructions (Form 160.54-M1)
•
Not in Brine Cooling mode
•
Smart Freeze is enabled.
•
Evaporator Temperature Sensor (RT7) or Evaporator Saturation Temperature is indicating a
temperature of less than 32.0°F
The chiller can be started after the temperatures are within 3.0°F of one another and the Operator
presses the WARNING RESET button.
Condenser – High Pressure Contacts Open
The contacts of the electro-mechanical high pressure safety device, located on the condenser shell,
have opened because this device has detected a pressure:
•
more than 204 PSIG (R134a)
The contacts will automatically close when the condenser pressure decreases to:
•
less than 160 PSIG (R134a)
The chiller can be started after the contacts close and the Operator presses the WARNING RESET
button.
Condenser – High Pressure
The condenser pressure, as sensed by the Condenser transducer, has increased to:
•
more than 180.0 PSIG (R134a)
•
more than 265.0 PSIG (R22)
The chiller can be started after the pressure decreases to:
•
less than 120.0 PSIG (R134a)
•
less than 205 PSIG (R22) and the Operator presses the WARNING RESET button.
For special order R134a high condenser temperature chiller applications, the Condenser
Temperature Range Setpoint is set to Extended. The trip/reset threshold is then 200/140 PSIG.
Condenser – High Pressure – Stopped
The condenser pressure exceeded 160.0 PSIG (R134a), 240.0 PSIG (R22) while the chiller was
stopped. High temperature condenser water flowing through the condenser while the chiller is
shutdown can cause a condenser high pressure condition resulting in loss of refrigerant. This safety
fault anticipates this problem by annunciating the condenser high pressure condition. The chiller
can be restarted after a Service Technician performs a special reset preset procedure contained in
OptiView Control Center – Service Instructions (Form 160.54-M1)
.
For special order R134a high condenser temperature chiller applications, the Condenser
Temperature Range Setpoint is set to Extended. The trip/reset is then 170/170 PSIG .
Condenser – Pressure Transducer Out Of Range
The Condenser Pressure transducer is indicating a pressure that is:
•
less than 6.8 PSIG (R134a)
•
less than 24.2 PSIG (R22)
•
or more than 300.0 PSIG (R134a or R22)
YK-EP Style B Centrifugal Chiller
210
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...