Pins 2-3:
+5VDC/0VDC SHARP LQ10D367, LQ10D368, LQ104V1DG61 and LG Semicon LP104V2-
W displays.
JP5*
Display Backlight power. Determines the power supply voltage applied to the Display Backlight
Inverter Board.
•
Pins 1-2:
+12VDC. SHARP LQ10D367, LQ10D368, LQ104V1DG61, LQ104V1DG81 and LG
Semicon LP104V2-W displays.
•
Pins 2-3:
+5VDC. Not used.
JP7*, JP8*
Display brightness control technique. Determines whether the display brightness is controlled by a
variable resistance or a variable voltage.
•
IN:
Variable voltage (0 to 5.0VDC). SHARP LQ10D367, LQ10D368, LQ104V1DG61, LQ104V1DG81
and LG Semicon LP104V2W displays.
•
OUT:
Variable resistance – not used.
JP10*
Factory mounted thermal flow sensor – evaporator connected to J14.
•
Pins 1-2:
Not used.
•
Pins 2-3:
Place shunt in this position
JP11*
Factory mountedthermal flow sensor – condenser connected to J14
•
Pins 1-2:
Not used.
•
Pins 2-3:
Place shunt in this position
JP12*
Not used
•
Pins 1-2:
Not used.
•
Pins 2-3:
Place shunt in this position
JP12*
Not used
•
Pins 1-2:
Not used.
•
Pins 2-3:
Place shunt in this position
JP14
Applies a 120 Ohm terminating resistor across the COM3 RS-485 port.
•
IN:
Not used.
•
OUT:
Normal position - no bias applied.
YK-EP Style B Centrifugal Chiller
244
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...