Refrigerant level control screen
Figure 12: Refrigerant level control screen
This screen displays a cutaway view of the chiller condenser, along with the liquid refrigerant level
sensor and the flow control valve. All setpoints relating to the liquid level control are maintained on
this screen. Through animation, the variable orifice position is displayed. In addition, the refrigerant
flow control valve (variable orifice) can be manually operated.
Note:
Requires a login access level of SERVICE.
Table 22: Display only fields
Field/LED name
Description
Condenser Refrigerant Level Displays the present position of the liquid level*.
Subcooler Effectiveness
The Subcooler Effectiveness is evaluated with the following
calculation and compared to a high and low limit. (Cond Sat Temp-
Drop Leg Ref Temp)/(Cond Sat Temp-Entering Cond Liq Temp). This
value is typically near 0.8 at design conditions.
Level Control State
Indicates one of the following states the level control routine is in:
Manual, Inactive, Startup Hold, Setpoint Ramp, PID Control, Hold.
Startup Delay Remaining
The level valve is held at the starting position until 15 seconds after
start to allow the system to stabilize. Then the valve position is
controlled by the PID loop. This read box displays the remaining
seconds until PID control.
Level Control Valve
Command
Indicates the valve command as a percentage of full open. It is only
displayed when the valve control method is analog.
39
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...