Economizer operation screen
Figure 15: Economizer operations screen
This screen shows various settings and information available to set up the economizer.
Table 32: Programmable
Field/LED
Access level Description
VGD
–
Displays the status of the VGD. It will show enabled or disabled.
Anti-Recycle
–
Displays the status for the Anti-Recycle timer. It will show enabled or
disabled.
Coastdown
Time
–
Displays the amount of time the economizer compressor spent in
coastdown.
Motor Auto
Lube Type
–
Set to P203, QLS401, Sleeve or None as appropriate.
Motor Heater
–
Set to Enable if a motor heater is present else Disabled.
Number of
starts.
Admin
Displays the number of starts that the economizer compressor has
accumulated.
Operating
Hours
Admin
Displays the number of economizer compressor operating hours.
49
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...