Hot gas bypass screen
Figure 19: Hot gas bypass screen
This screen displays a cutaway view of the Hot Gas Bypass Valve. The setpoints relating to the
Hot Gas Bypass Control are maintained on this screen. Related Hot Gas control parameters are
displayed for reference. The Hot Gas Valve can be manually controlled from this screen. Through
animation, the relative valve position is displayed. The parameters displayed on this screen vary
according to the software version and the selection made for the Motor Communications Protocol
Setpoint when equipped with Variable Speed Drive (VSD) or Medium Voltage Variable Speed Drive
(MVVSD).
Table 43: Display only
Field/LED name
Description
Valve Position
Displays the present position of the Hot Gas Valve as a value
between 0% (closed) to 100% (full open). By animation, the valve is
shown in its relative position. The actual position of the valve does
not match the percentage displayed in the Valve Position Box. The
actual levels and their relative values can be read from Table 44.
Pre-Rotation Vanes Position Displays the present Pre-Rotation Vanes position as a value between
0% (closed) and 100% (full open).
Delta P/P
Displays the chiller head pressure calculated as (condenser pressure
– evaporator pressure/evaporator pressure).
Temperature Differential
(LCHLT – Setpoint)
Displays the difference between the Leaving Chilled Liquid
Temperature and the Leaving Chilled Liquid Temperature Setpoint.
57
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...