Table 48: Programmable
Button
Access level Description
Shutdown
(Enabled/
Disabled)
Operator
Allows the user to select whether the chiller will shutdown or
continue to run when an Excess Surge situation has been detected.
If this setpoint is Enabled and the Extended Run Setpoint is
Disabled, a safety shutdown is performed when the Surge Window
Count exceeds the Count Limit Setpoint.
If this setpoint is Enabled and the Extended Run Setpoint is Enabled,
a safety shutdown is performed if the Surge Window Count exceeds
the Count Limit Setpoint at the completion of the 10 minute
Extended Run period.
Surge Protection – Excess Surge is displayed with either shutdown.If
this setpoint is Disabled, refer to operation under Count Limit in this
section.
•
If equipped with a compressor Variable Speed Drive (VSD),
the VSD output frequency must be at maximum before
the Shutdown feature is implemented or Surge Warning
messages are displayed.
•
If equipped with a VSD and Hot Gas Bypass (Enabled), the VSD
output frequency must be at maximum and the Hot Gas Valve
must be at 100% before the Shutdown feature is implemented
or Surge warning messages are displayed.
Extended
Run
(Enabled/
Disabled)
Operator
Allows the user to select the surge correction/avoidance Extended
Run mode. This will be implemented when an Excess Surge situation
is detected as follows:
Anytime the Surge Window Count exceeds the Count Limit, the Pre-
Rotation Vanes are driven closed for the next 10 minutes. While
this load inhibit is in effect, WARNING – SURGE PROTECTION –
EXCESS SURGE LIMIT is displayed. When 10 minutes have elapsed,
the warning message and load inhibit are automatically cleared,
provided the Surge Window Count is less than or equal to the Count
Limit. If the Shutdown Setpoint is Enabled, and the Surge Window
Count exceeds the Count Limit at the completion of this period, a
safety shutdown is performed and Surge Protection – Excess Surge
is displayed.
If the Hot Gas Bypass control is Enabled, the Hot Gas Bypass
Valve position must be 100% before the Extended Run mode is
implemented. If the chiller is equipped with a Compressor Motor
Variable Speed Drive, output frequency must be at full speed
(50Hz/60Hz) before the Extended Run mode is implemented. If the
chiller is equipped with both Hot Gas Bypass and Compressor Motor
Variable Speed Drive, both of the conditions must be met before
Extended Run is implemented.
YK-EP Style B Centrifugal Chiller
62
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...