Table 53: Display only
Field/LED name
Description
ACC Surge Detected (LED)
Only displayed if equipped with a VSD or MVVSD. Illuminates
momentarily when a surge is detected by the ACC function in
the Microboard, while the drive is running at less than maximum
frequency.
VGD Count
Displays the number of times the Stall Detector Board output
voltage goes above the High Limit Setpoint. The count can be reset
with an ADMIN access level using the VGD CYCLE COUNT key on the
VGD SETPOINTS Screen.
VGD Time
( __Days __Hrs __Min __Sec)
Displays the accumulated time the Stall Detector Board output
voltage is greater than the High Limit Setpoint while the chiller is
running.
Control Status
Displays the current state of the VGD control. The states are: Stall
Waiting, Stall Reacting, Probing, Surge Reacting, Surge Waiting, Hot
Gas Override.
Time Remaining
While the VGD is in the Stall Waiting State, displays the time
remaining in the Probe Wait Time interval (value programmed as
the Probe Wait Time setpoint).
Table 54: Programmable
Button
Access level Description
Surge React
–
1 to 30 seconds; default 5
Specifies the length of the close pulse applied to the VGD in
response to a surge.
PRV Offset
–
0 to 5%; default 3
If the VGD control is in the Stall Waiting state and the Pre-Rotation
Vanes position changes by more than this value, the Probing state
will be entered. If the PRV Offset is set to 0%, the Stall Waiting state
is performed based only on the Probe Wait Time setpoint interval.
Probe Wait
–
0.5 to 15 minutes; default 10
Specifies how long the VGD control remains in the Stall Waiting or
Surge Waiting states before entering the Probing state.
Open Pulse
–
1 to 5 seconds; default 2
Specifies the length of the open pulse applied to the VGD during 10
second periods while in the Probing state.
67
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...