Table 56: Display only
Field/LED name
Description
Discharge Pressure
Displays the current discharge pressure of the economizer
compressor.
Economizer Pressure
Shows the pressure within the economizer.
Head Pressure
Shows the head pressure of the economizer.
PRV Position
Displays the position of the pre rotation vanes in percent. Fully open
is 100% and fully closed is 0%.
VGD Control State
Shows the current state of the VGD Control. It will show various
messages as follows:
•
Undefined
•
Disabled
•
Stall Waiting
•
Probing
•
Stall Reacting
•
PRV Override
•
Sensor Failure Override
•
Extreme Stall Override
•
Manual Hold
•
Manual Open
•
Manual Close
•
Inactive
Table 57: Programmable
Button
Access level Description
VGD Actuator Service
Displays the current state of the VGD Actuator. It will show either
Auto or Manual.
Open (with
LED)
Service
Pressing this button will send a command to open the VGD. The LED
will indicate on.
Close (with
LED)
Service
Pressing this button will send a command to close the VGD. The LED
will indicate on.
Hold
Service
Pressing this button will hold the VGD in it's current position.
Auto
Service
Pressing this button returns the VGD to automatic
Table 58: Navigation
Button
Access level Description
Home
Service
Returns user to HOME Screen.
Economizer
Compressor Service
Pressing this button will return to the Economizer Compressor
Screen.
Setpoints
Service
Pressing this button will navigate to the Economizer VGD Setpoints
Screen.
YK-EP Style B Centrifugal Chiller
70
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...