Table 60: Programmable
Button
Access level Description
Stall Wait
Time
Service
(0.5 to 15 minutes, Default 10 minutes)
After the VGD control detects a stall and enters Stall Wait State. It
will wait for 10 minutes before going into the probing (Open) mode.
Open Pulse
Service
(1 to 5 seconds, Default 2 seconds)
In the Probing State, VGD opens in pulse. The pulse length is 10
seconds. The VGD will open for 2 seconds and hold during the rest
of the pulse period (8 seconds). This pulse repeats the 10 second
pulse over and over again until the stall voltage is higher than the
high limit.
High Limit
Service
(0.35 to 1.20V, Default 0.8V)
If stall voltage is higher than high limit of 0.8V, the VGD control
enters the stall react state that closes the VGD. It will keep closing
the VGD until stall volt is lower than the low limit 0.5V.
Low Limit
Service
(0.30 to 0.79V, Default 0.50V)
When stall voltage is lower than low limit, the VGD control enters the
Wait state.
Table 61: Navigation
Button
Access level Description
Home
Service
Returns user to HOME Screen.
Economizer
VGD
Service
Pressing this button will return to the Economizer VGD screen.
73
YK-EP Style B Centrifugal Chiller
Summary of Contents for YK-EP
Page 2: ...2 YK EP Style B Centrifugal Chiller...
Page 6: ...6 YK EP Style B Centrifugal Chiller...
Page 227: ...Figure 72 Sample printout of Status 227 YK EP Style B Centrifugal Chiller...
Page 228: ...Figure 73 Sample printout of Status cont YK EP Style B Centrifugal Chiller 228...
Page 229: ...Figure 74 Sample printout of Setpoints 229 YK EP Style B Centrifugal Chiller...
Page 230: ...Figure 75 Sample printout of Setpoints cont YK EP Style B Centrifugal Chiller 230...
Page 231: ...Figure 76 Sample printout of Schedule 231 YK EP Style B Centrifugal Chiller...
Page 232: ...Figure 77 Sample printout of a Sales order YK EP Style B Centrifugal Chiller 232...
Page 233: ...Figure 78 Sample printout of a Sales order cont 233 YK EP Style B Centrifugal Chiller...
Page 234: ...Figure 79 Sample printout of History YK EP Style B Centrifugal Chiller 234...
Page 235: ...Figure 80 Sample printout of History cont 235 YK EP Style B Centrifugal Chiller...
Page 236: ...Figure 81 Sample printout of a security log report YK EP Style B Centrifugal Chiller 236...